Description
Key Technical Specifications
| Parameter | Value | Confidence |
|---|---|---|
| Model | TC-FPCXX2 (alt. TK-FPCXX2) | Confirmed |
| Manufacturer | Honeywell | Confirmed |
| Function | Chassis power supply module | Confirmed in Honeywell C200 parts list |
| Input voltage | 120/240 VAC nominal | Stated in parts list |
| Line frequency | 50/60 Hz | Verify with OEM datasheet |
| Output | DC rails for C200 chassis / I/O | Verify with OEM datasheet |
| Output current / wattage | Not published | Verify with OEM datasheet |
| Mounting | Slot-mount, C200 chassis (e.g., TC-FXX102 10-slot, TC-FXX132 13-slot) | Inferred from parts list |
| Redundancy | Chassis-level; confirm scheme | Verify with OEM datasheet |
| Protections | Overvoltage / overcurrent / short-circuit typical for class | Verify with OEM datasheet |
| Comms | None — it’s a power supply | Confirmed by function |
| Status | Discontinued; no current Honeywell part number published | Confirmed |
Product Introduction
A dead power supply in a C200 chassis doesn’t fail gracefully. It takes the controller, the I/O, and the loop with it — and if you don’t have a spare on the shelf, you’re explaining a plant outage to a plant manager while a broker quotes you a six-week lead time. That’s the actual risk this part number carries.TC-FPCXX2 is Honeywell’s 120/240 VAC chassis power supply for the C200 family. It sits in the rack, eats line voltage, and feeds DC to everything downstream. The reason engineers care is simple: it’s a direct drop-in. Same slot, same connector, same wiring. No reconfiguration, no re-commissioning, no logic download.Two honest cautions. First, the part number is polluted — half the listings online describe something that isn’t a power supply, so buy from the drawing, not from a web description. Second, the TK- prefix and TC- prefix are used interchangeably by suppliers, but confirm the revision against the unit you’re replacing. I’ve seen mixed revisions on the same shelf.
Quality SOP & Tech Pitfalls
The Lab Report (SOP)
- Visual and counterfeit check — nameplate legibility, mold marks, re-soldered pins, capacitor bulge or leakage.
- Input continuity and insulation resistance, line-to-chassis, megger at 500 VDC.
- Bench energization on a test rack at both 120 VAC and 240 VAC input.
- Output voltage measured at no-load and at rated load with a Fluke 115; ripple observed on a scope.
- Protection functions exercised — short-circuit and overcurrent trip confirmed, recovery observed.
- Serial number, revision, and output readings photographed and logged.
- Anti-static bag, foam-packed, sealed, photographed before shipping.
The Engineer’s WarningTwo mistakes dominate.First: buying the wrong module because the web description was wrong. I’ve seen this part number sold as an “output module” and as a “field power computer module” with a Pentium processor. If you order based on a listing description, you’ll get a box that doesn’t fit your slot. Order from your panel drawing.Second: mixing revisions in a redundant pair. If your chassis runs two supplies, both units should be the same revision. A mismatched pair can fight over load sharing or trip the redundancy alarm.Field disaster: a plant ordered a “TC-FPCXX2” from a broker who shipped a TC-FPDXX2 — the 24 VDC supply. Same rack, same slot, wrong voltage. The tech caught it at the nameplate. Had he not, the chassis would have been fed 24 VDC instead of the rail it expected. Nine days of spare-hunting, avoided by one label check.
Installation & Configuration Guide
1. Pre-Installation ⚠️
Shut down the controller and open the incoming AC breaker for the chassis. Confirm 0 V at the power supply terminals with a multimeter. Wait 60 seconds for stored energy to bleed. Photograph the incoming AC wiring, the slot position, and the nameplate of the old unit.2. Removal
Tag each AC line and neutral/ground conductor before loosening. Release the slot clips or mounting hardware evenly — don’t pry from one corner. Pull straight out, keeping the module level so the backplane connector doesn’t bind.3. Installation
Confirm the replacement’s nameplate voltage and revision match the old unit before it goes in the slot. Seat the module fully until the connector is fully mated and the clips engage. Torque AC terminals to panel spec — no more. Verify ground continuity to chassis.4. Power-On & Testing
Restore AC. Measure input voltage at the terminal block, not at the breaker. Confirm output DC rails at the bus with a multimeter. Watch the chassis status LEDs through the boot sequence. Verify the controller comes online and I/O responds. Log output voltage and ripple.
Compatible Replacement Models
- ✅ Drop-in Replacement: Another TC-FPCXX2, same revision. Zero engineering work. Price spread is wide — I found ¥1,000–¥1,123 from two suppliers and ¥3,660 from a third, for the same part number. That’s not a price list; that’s an unregulated surplus market.
- ⚠️ Software Compatible: TK-FPCXX2, the alternate-prefix version. Same function, but confirm the revision and connector pinout before install. Budget 2–4 hours plus a commissioning window.
- ❌ Hardware Mod Required: A modern Honeywell power supply (PKS/Experion class) or a third-party DIN-rail supply. New chassis, new wiring, new grounding. Only worth it if you’re replacing the whole C200 rack — not to fix one dead supply.
Frequently Asked Questions (FAQ)
Can I hot-swap this safely?
No. It’s fed from line voltage. Open the incoming AC breaker, verify zero volts, then work. Hot-swapping a chassis power supply risks arcing and a hard controller fault.Is it really in stock?
Treat “in stock” on a discontinued Honeywell part with suspicion. Some listings claim “充足” supply, others quote a lead time. Ask for a photo of the actual unit with your order number handwritten on paper beside it. If they stall, walk.Is TC-FPCXX2 the same as TK-FPCXX2?
Suppliers use them interchangeably, and both appear in the same parts lists. Functionally they’re the same part. Still, confirm the revision against the unit you’re replacing — especially in a redundant chassis.Does it have a processor or communication port?
No. Despite what some listings claim, this is a power supply. No Pentium, no memory, no Ethernet, no Modbus. If your listing mentions an operating system, it’s describing a different product.What’s the output voltage?
Not published in any public source I found. It’s a DC rail for the C200 chassis. Get it from your panel drawing or from the nameplate of the unit you’re replacing — don’t guess.How long is the warranty?
One year from delivery against manufacturing defects. Note: capacitor wear on a 20-year-old surplus unit isn’t a manufacturing defect, and I’d rather say that now than argue in month nine.Should I buy two?
Yes, if the chassis feeds a controller you can’t afford to lose. Lead times on discontinued Honeywell DCS parts run weeks, and the next batch may not exist.




Tel:
Email:
WhatsApp: 