ABB REM545BG227AAAB | Relion 545 Motor Protection Relay, Legacy IED

  • Model: REM545BG227AAAB
  • Brand: ABB
  • Series: Relion 545 / REM545 motor protection and control terminal
  • Core Function: Protects medium-voltage synchronous and asynchronous motors by monitoring current, voltage, thermal state, and fault conditions, then tripping the breaker before the rotor locks or the stator insulation cooks.
  • Type: Motor protection IED with programmable logic, measurement, and communication
  • Key Specs: 1 A / 5 A CT inputs; auxiliary supply typically 24–250 V DC or 100–240 V AC; multiple binary inputs and output relays; communication options vary by order code (SPA-bus, Modbus RTU, Profibus-DP, IEC 60870-5-103, IEC 61850 via adapter)
Category:

Description

Key Technical Specifications

Parameter Specification
Product Type Motor protection and control IED
Manufacturer ABB
Series Relion 545 / REM545
Model REM545BG227AAAB
CT Inputs 1 A or 5 A nominal, via external current transformers
VT Inputs Voltage inputs for voltage-dependent protection functions
Auxiliary Supply Typically 24–250 V DC or 100–240 V AC, 50/60 Hz (verify per nameplate)
Binary I/O Multiple binary inputs and output relays; exact count depends on option pack
Communication SPA-bus, Modbus RTU, Profibus-DP, IEC 60870-5-103; IEC 61850 via SPA-ZC adapter depending on variant
Protection Functions Thermal overload, start-up supervision, stall/locked-rotor, phase unbalance, earth fault, overcurrent, undercurrent, voltage-dependent protection, frequency protection
Programmable Logic Built-in scheme logic for interlocks, permissives, trip/alarm routing
Mounting Panel flush-mount; 19-inch rack mount with adapter
Operating Temperature Typically -10 °C to +55 °C; confirm against nameplate for this revision
Standards / Compliance IEC 60255 series; marine/offshore certification available for REM545 family

 

Product Introduction

The ABB REM545BG227AAAB sits in the REM545 family of motor protection terminals — the kind of relay you find guarding a medium-voltage boiler feed pump or a large crusher drive where a nuisance trip costs more than the spare part. It is not a generic PLC card or a simple overcurrent relay. It combines thermal replica modeling, stall protection, start supervision, earth-fault detection, voltage-dependent protection, and programmable scheme logic in one panel-mounted IED.Engineers keep REM545 units in service because replacing one failed relay is far cheaper than re-engineering an entire protection scheme during a short outage window. The REM545 family has been declared not active since 2022, so BG227AAAB should be treated as a legacy spare. The exact communication ports, binary I/O count, and trip contact ratings depend on the option code — I would never assume them from a generic REM545 datasheet. Match the nameplate, the installed option modules, and the PCM600 parameter set before energizing.

Quality SOP & Tech Pitfalls

The Lab Report (SOP)

  1. Visual and counterfeit check: verify ABB branding, model code REM545BG227AAAB, hardware revision, and serial number.
  2. Connector inspection: check CT/VT terminals, binary I/O connectors, communication ports, and front-panel HMI.
  3. Insulation and continuity check: use a Fluke 115 or equivalent multimeter on auxiliary supply, trip circuits, and binary I/O before applying power.
  4. Auxiliary power-up test: apply rated control voltage and verify display, LEDs, and watchdog status.
  5. I/O verification: inject test signals into CT/VT inputs and confirm binary input response and output relay operation.
  6. Communication test: verify SPA-bus, Modbus RTU, Profibus-DP, or IEC 61850 connectivity per the installed option pack.
  7. Firmware and parameter logging: record firmware version, parameter set, and event log; compare with the original relay backup.
  8. Packing: anti-static bag, terminal protection, and photo-backed test record.

The Engineer’s Warning (Pitfalls)

  • The BG227AAAB suffix is an option code. It defines communication interfaces, I/O configuration, and possibly trip contact ratings. A physically identical REM545 with a different suffix will not behave the same.
  • I once watched a plant swap a REM545 without restoring the PCM600 parameter set. The relay powered up fine — then tripped the feeder on the first start because the thermal replica and stall timers were factory defaults. Two hours of downtime for a five-minute parameter restore.
  • CT polarity matters. Reversed CT wiring can disable differential or unbalance protection and create false thermal accumulation.
  • Do not assume IEC 61850 is present. Many REM545 units only support IEC 61850 through a SPA-ZC adapter. Check the rear communication module before promising GOOSE messaging to the SCADA team.

 

Installation & Configuration Guide

  1. Pre-Installation ⚠️
    • Follow site LOTO and switchgear safety procedures.
    • Confirm the breaker is open and the CT secondary circuits are safely handled.
    • Photograph the existing relay: nameplate, option modules, terminal wiring, DIP switches or configuration labels, LED status, and communication cabling.
    • Export the parameter set from the original relay using PCM600 if still accessible.
  2. Removal
    • Label every wire before disconnecting. CT circuits must never be opened while energized.
    • Note the terminal block positions for CT, VT, binary I/O, trip coils, and communication.
    • Release the mounting clamps and withdraw the relay carefully.
  3. Installation
    • Copy all configuration first. Parameter sets, I/O mapping, communication addresses, and protection settings must match the commissioned values.
    • Inspect rear connectors and communication modules for damage or missing option cards.
    • Seat the replacement REM545BG227AAAB firmly and secure the mounting hardware.
    • Reconnect CT, VT, binary I/O, trip circuits, and communication exactly as labeled.
  4. Power-On & Testing
    • Verify auxiliary supply voltage and polarity before energizing.
    • Check the boot sequence, display, and LED indicators.
    • Confirm CT/VT measurements against known references.
    • Test binary inputs, trip outputs, and alarm contacts.
    • Verify communication with SCADA or the local HMI.
    • Do not return the motor to service until protection settings, trip logic, and event recording are confirmed.

Compatible Replacement Models

| Compatibility Tier | Model / Option | Notes |
| :— | :— |
| ✅ Drop-in Replacement | ABB REM545BG227AAAB, same revision and option modules | Lowest risk; restore original PCM600 parameter set. |
| ⚠️ Software Compatible | Other REM545 variants with matching I/O and communication options | Requires parameter migration, I/O verification, and possible firmware alignment. |
| ❌ Hardware Mod Required | ABB Relion 615/620/650 series (e.g., REM615, REM620) | Requires panel modification, wiring changes, PCM600 reconfiguration, and full commissioning. |

 

Frequently Asked Questions

Is REM545BG227AAAB still in production?
No. The REM545 family has been declared not active since 2022. Availability comes from surplus stock or authorized legacy channels. Always request nameplate photos, revision codes, and test records.Can I replace it with any REM545 unit?
No. The BG227AAAB option code determines communication interfaces, I/O configuration, and possibly trip contact ratings. A different REM545 suffix may lack the required ports or have different binary I/O assignments.Does it support IEC 61850?
Only if the installed option pack includes IEC 61850 support or a SPA-ZC adapter. Many REM545 units ship with SPA-bus, Modbus RTU, or Profibus-DP instead. Check the rear module before assuming GOOSE capability.What happens if I power it up without restoring parameters?
The relay will boot with factory defaults. Protection settings, thermal models, I/O mapping, and communication addresses will be wrong. That is a reliable way to create nuisance trips or leave the motor unprotected.Can I hot-swap this relay?
Only if site procedures and the switchgear design allow it. Trip circuits, binary interlocks, and communication redundancy must be verified before attempting a live replacement. In most cases, a planned outage is the safer path.How do I confirm the correct option configuration?
Read the full nameplate code, inspect the rear communication and I/O modules, and compare with the original relay’s PCM600 backup. If the old relay is unreadable, pull the configuration from the SCADA event logs or the plant’s protection setting records.