ABB REM545 Machine Terminal | Motor and Generator Protection Relay | In Stock

  • Model: REM545
  • Brand: ABB
  • Series: Relion / REM545 Machine Terminal
  • Core Function: Integrated motor and generator protection, measurement, control, condition monitoring, and communication in a single terminal for medium-voltage rotating machines.
  • Type: Machine Protection Terminal
  • Key Specs: Differential and thermal overload protection; RTD/mA temperature monitoring option; PLC logic; Modbus / SPA / LON / IEC communication support depending on configuration.
Category:

Description

Key Technical Specifications

Parameter Specification
Manufacturer ABB
Series Relion / REM545
Product Type Machine Terminal for Motor and Generator Protection
Typical Application Medium-voltage synchronous and asynchronous motors, generators, generator-transformer units
Protection Functions Differential, overcurrent, ground fault, thermal overload, unbalanced load, over/under voltage, frequency protection, start supervision
Measurement Current, voltage, power, power factor, frequency, energy
Control Local and remote breaker control, interlocking, status indication
Condition Monitoring Breaker status, trip circuit supervision, RTD/mA temperature monitoring option
Communication SPA bus, LON bus, Modbus, IEC depending on configuration
PLC Logic Integrated programmable logic for automation and sequence control
Auxiliary Power Typically universal AC/DC auxiliary supply; confirm from nameplate
CT/VT Input Via external current and voltage transformers
Mounting Panel-mount / switchgear integration
Status Legacy product; confirm availability and replacement path

 

Product Introduction

The REM545 is ABB’s machine terminal for protecting medium-voltage motors and generators. Unlike a simple overcurrent relay, it combines differential protection, thermal overload modeling, start supervision, voltage/frequency protection, and condition monitoring in one unit. That makes it suitable for critical drives, generator sets, pump stations, mills, crushers, and process machines where an unexpected trip can stop an entire production line.The REM545 places it in the machine protection family, while the following characters define display type, sensor option, auxiliary power, I/O configuration, and communication modules. In brownfield plants, this terminal is often found in switchgear panels protecting synchronous motors, large asynchronous motors, or small to medium generators.From an integration standpoint, the REM545 remains attractive because it supports multiple communication protocols and includes PLC logic. That allows local interlocks, permissive logic, and sequence control without adding an external PLC. However, because it is now a legacy platform, replacement planning should include verification of firmware, communication settings, and available I/O.

Quality SOP & Tech Pitfalls

The Lab Report (SOP)Each unit is inspected before shipment:

  1. Nameplate verification — model, ordering code, serial number, auxiliary voltage, and firmware.
  2. Visual inspection — front panel, display, terminals, connectors, and mounting hardware.
  3. Auxiliary power-up test — confirm normal boot and display operation.
  4. I/O check — verify binary input and output relay status.
  5. Communication port inspection — check SPA, LON, Modbus, or fiber/optical interfaces where fitted.
  6. Setting review — confirm existing configuration is readable if the unit is supplied powered.
  7. Packaging — anti-static protection, sealed bag, and inspection report. Video available on request.

The Engineer’s Warning (Pitfalls)First, do not replace by frame size alone. Another REM545 or REM543 may look similar but have different I/O, communication modules, or auxiliary voltage. Swapping without checking the ordering code can break interlocks or communication.Second, confirm the communication option. REM545 terminals may support SPA, LON, Modbus, or IEC depending on configuration. If the relay connects to a SCADA or substation automation system, the protocol must match the existing architecture.Third, verify RTD/mA and binary I/O mapping. If the original unit monitored stator winding temperature, bearing temperature, or external trip signals, the replacement must provide the same inputs. Otherwise, alarms may disappear without any visible fault.

 

Installation & Configuration Guide

1. Pre-Installation ️

  • Lock out auxiliary and secondary power.
  • Photograph existing wiring, terminal labels, and communication connections.
  • Record the original ordering code and firmware version.
  • Confirm CT/VT ratios and protection settings.

2. Removal

  • Disconnect auxiliary power first.
  • Label all binary I/O, CT/VT, RTD, and communication cables.
  • Remove the unit carefully to avoid damaging rear connectors.
  • Check cable tags against the original drawings.

3. Installation

  • Mount the replacement REM545 in the same position.
  • Reconnect auxiliary power, CT/VT, binary I/O, and communication cables.
  • Verify RTD/mA module wiring if temperature monitoring is used.
  • Confirm communication wiring matches the original protocol.

4. Commissioning

  • Apply auxiliary power and check display operation.
  • Verify CT/VT scaling and phase rotation.
  • Test binary inputs and trip outputs.
  • Confirm communication with SCADA or HMI.
  • Perform secondary injection or functional testing where possible.
  • Validate trip logic, alarms, and temperature monitoring before returning to service.

Compatible Replacement Models

Compatibility Model Notes
Drop-in Replacement REM545 (same ordering code) Same ordering code. Preferred replacement. Verify firmware and I/O.
️ Possible Alternative REM545 with different suffix May work if auxiliary voltage, I/O, communication, and settings match. Requires engineering review.
️ Series Alternative REM543 Smaller machine terminal family. Not automatic drop-in; I/O and functions may differ.
️ Modern Alternative REM615 Newer motor protection relay. Requires setting migration, I/O verification, and communication validation.
Not Directly Compatible REF545 / REF615 Feeder protection terminals. Different application focus and function set.

 

Frequently Asked Questions (FAQ)

Q: What does the REM545 protect?
It is a machine terminal for motors and generators, typically used in medium-voltage switchgear. It provides differential, overcurrent, thermal overload, ground fault, voltage, frequency, and start supervision functions.Q: Can I replace it with any REM545 unit?
No. The suffix defines auxiliary power, display, I/O, communication, and option modules. A different REM545 code may not match the existing wiring or settings.Q: Does it support IEC communication?
Some REM545 configurations support IEC through an adapter or communication module. Others use SPA, LON, or Modbus. The exact capability depends on the installed option.Q: Is REM545 still in production?
The REM545/REF545 family is considered legacy. ABB has moved to newer Relion platforms, so availability should be confirmed per ordering code.Q: Can it monitor motor temperature?
Yes, when equipped with the RTD/mA option. It can monitor stator winding, bearing, or process temperature signals.Q: What should I check before buying a replacement?
Confirm the full ordering code, auxiliary voltage, communication protocol, RTD/mA option, binary I/O count, and existing protection settings.Q: Do you provide test reports?
Yes. Each unit can be supplied with an inspection and functional test report. Additional bench testing can be arranged on request.