ABB PM861AK01 | 3BSE018157R1 AC 800M CPU In Stock

  • Model: PM861AK01 (Material No. 3BSE018157R1)
  • Brand: ABB
  • Series: AC 800M / 800xA
  • Core Function: Executes IEC 61131-3 control logic and manages S800 I/O and CEX bus communication.
  • Type: Processor Unit (CPU)
  • Key Specs: 48MHz MPC860 processor; 16MB total memory; dual 10Mbit/s Ethernet ports
Category:

Description

Key Technical Specifications

Parameter Specification
Processor MPC860 @ 48MHz
Execution Speed 0.23 ms / 1000 Boolean operations
Total Memory 16 MB (7.155 MB app RAM, 2 MB Flash)
Power Supply 24 VDC (19.2 – 30 VDC range)
Power Consumption 6.0 W typical (10.3 W max)
Ethernet Ports 2x RJ45 (CN1, CN2) @ 10Mbit/s
Serial Ports COM3 (RS-232C), COM4 (Isolated RS-232C)
CEX Bus Capacity 12 communication modules
I/O Capacity 96 modules (non-redundant) / 84 (redundant)
Redundancy Supports CPU redundancy (RCU link)
Operating Temp 0°C to +60°C
Protection Class IP20

 

Product Introduction

I’ve pulled more of these out of 800xA racks than I care to count. The PM861AK01 is the workhorse CPU for ABB’s AC 800M platform. It’s not going to win any speed contests against modern ARM-based controllers, but it runs the Control Builder M logic without complaining. The 48MHz MPC860 chip crunches through standard FBD and ST code just fine.What engineers actually care about is the redundancy. You pair two of these up with an RCU link cable, and you get a bumpless transfer in under 10 milliseconds if the primary fails. That’s the real value. Just remember this: the IP20 rating means it lives in a clean control cabinet. If you mount it somewhere with conductive dust or excessive vibration, the backplane connections will eventually fail.

Quality SOP & Tech Pitfalls

The Lab Report (SOP)
Before anything ships, it goes through my bench protocol.

  1. Visual inspection. I’m checking for shipping damage, bent DIN clips, and counterfeit label fonts.
  2. Bench power-up with a Fluke 87V. I verify the 24 VDC input draws the correct 6.0 W typical load.
  3. Communication test. I ping the CN1 and CN2 Ethernet ports and verify the MAC address matches the hardware label.
  4. Firmware and hardware revision logging against the OEM database.
  5. Anti-static bagging. ESD destroys these boards instantly.

The Engineer’s Warning (Pitfalls)
The number one killer of these modules is swapping the CPU without swapping the TP830 base plate. The base plate holds the unique Ethernet MAC address. If you drop a replacement PM861AK01 into an old base plate without updating the MAC address in the 800xA system tree, the controller will never come online. You’ll spend hours chasing a phantom network fault.Another trap? The lithium battery. It’s a 3.6V internal cell. If the controller sits unpowered on a shelf for years, that battery dies. When you finally power it up, the real-time clock is reset, and your historical data logs are corrupted. Always check the clock after a long storage period.

 

Installation & Configuration Guide

Phase 1: Pre-Installation
⚠️ Lockout the 24 VDC supply.
Photograph the existing terminal block and network drops. Note the exact slot position in the rack. If you’re replacing a single CPU in a redundant pair, put the system in manual mode first.Phase 2: Removal
Label every wire. Use proper wire markers, not sharpie on electrical tape.
Release the DIN rail clips using the slide-and-lock mechanism. Pull the module straight off the base plate. Don’t pry against the PCB.Phase 3: Installation
Mount the new PM861AK01 onto the TP830 base plate. Ensure the MAC address on the new base plate matches the system configuration. If it doesn’t, you must update it in Control Builder M before downloading.
Torque the PE ground screw to spec.
Reconnect the 24 VDC, Ethernet drops, and serial cables.Phase 4: Power-On & Testing
Apply 24 VDC. Watch the LED boot sequence. You’re looking for a solid green status LED, no flashing fault codes.
Open Control Builder M. Verify the controller is recognized on the control network.
Download the application. Watch the task execution times. If they’re exceeding 100ms, you might have a communication bottleneck on the CEX bus.

Compatible Replacement Models

  • ✅ Drop-in Replacement: PM861AK01 (Same material number). 100% hardware and firmware match. Just verify the base plate MAC address.
  • ⚠️ Software Compatible: PM861A (Base model without the K01 kit). Requires sourcing a separate TP830 base plate and potentially a firmware flash to match the existing system version.
  • ❌ Hardware Mod Required: PM864 / PM865. Higher performance CPUs, but they require a different base plate and may require a full system upgrade in 800xA.
  • ❌ Hardware Mod Required: PM891. Redundant CPU with dual RCU links. Requires a complete rack reconfiguration and new cabling.

 

Frequently Asked Questions (FAQ)

Can I hot-swap this module safely?
Yes, if you have a redundant CPU pair configured. Put the system in manual mode, pull the faulty CPU, and slide the new one in. The RCU link will handle the synchronization. If you’re running a single CPU, hot-swapping will drop your I/O and trip the process. Don’t do it.What happens if I mix up the CN1 and CN2 Ethernet ports?
Nothing catastrophic, but it breaks the network redundancy design. CN1 and CN2 are meant to connect to separate physical control network segments. If you plug both into the same switch, you lose the redundancy benefit. Keep them on separate VLANs or physical switches.Can I use a third-party CompactFlash card?
The PM861AK01 uses a CompactFlash interface for firmware and program storage. You can use a third-party card, but it must be formatted correctly and loaded with the exact firmware version matching your 800xA system. Verify the OEM manual for the exact partition layout before attempting this.How do I know if the 3.6V lithium battery is dead?
Power up the controller and check the real-time clock in Control Builder M. If the date resets to a default value (like Jan 1, 2000), the battery is dead. You’ll need to replace the internal cell or the entire CPU board, depending on the revision.Why is my CEX bus throwing communication errors?
Check your BC810 splitters. The CEX bus is highly sensitive to termination and grounding. If you’ve added too many communication modules (max 12) or the bus supply current exceeds 2.4A, you’ll get dropped packets. Verify your module count and power draw.Does it come with a warranty?