Key Technical Specifications
| Parameter | Specification |
|---|---|
| Full Model | MVTU11K1CD0751G |
| Manufacturer | ALSTHOM / GE Vernova |
| Product Type | Definite time AC undervoltage relay |
| Primary Function | AC undervoltage protection with timed output |
| Voltage Input | AC supply; rated voltage variant-dependent, commonly 110 VAC or 220 VAC at 50/60 Hz |
| Operating Characteristic | Undervoltage trip with adjustable definite-time delay |
| Logic Capability | Programmable state sequencing for interlocking logic |
| Output Contacts | Multiple isolated relay contacts (NO/NC) |
| Contact Rating | Verify against nameplate; typical MV-series contacts rated for several amps at AC/DC resistive |
| Isolation | Galvanic isolation between input, output, and supply circuits |
| Mounting | Panel-mount or DIN-rail-mount relay |
| Supply Status | Legacy spare; verify nameplate, suffix code, and test records |
Product Introduction
Undervoltage faults don’t announce themselves with drama. The motor keeps spinning, the VFD keeps humming, and then—during the next voltage dip—the whole process stalls because the protection logic never saw the warning. The MVTU11K1CD0751G sits in that gap. It is an ALSTHOM MV-series definite-time undervoltage relay, now under the GE Vernova product lineage, used to detect AC supply voltage drops and initiate timed trips or interlocks before equipment runs into trouble.What makes this unit stick around in legacy panels is the combination of straightforward undervoltage measurement with built-in programmable state sequencing. You do not always need a separate PLC ladder rung just to handle a voltage-dip interlock. I have seen these on LCI drive interfaces and plant auxiliary supply panels where a clean, deterministic undervoltage trip is worth more than a fancy communication module. The K1CD0751G suffix is the part that matters—change it, and you may change the voltage rating, contact set, or logic behavior.
Quality SOP & Tech Pitfalls
Lab Report (SOP)
- Visual inspection: nameplate, full suffix code, terminal condition, and signs of thermal stress.
- Counterfeit check: compare housing, labeling, and terminal layout against known MV-series units.
- Insulation and continuity checks with a multimeter such as a Fluke 115.
- Auxiliary supply verification at the rated AC voltage.
- Functional test: apply reduced AC voltage and verify undervoltage trip after the set delay.
- Verify output contact operation (NO/NC) and any indicator behavior.
- Record suffix code, serial number, and test results; seal in anti-static packaging.
Engineer’s Warning (Pitfalls)
The biggest mistake with MVTU11 units is treating the base model as sufficient. MVTU11 is the family; K1CD0751G defines the actual wiring, voltage rating, and logic configuration. I have seen a plant replace an undervoltage relay based only on “MVTU11” and end up with wrong contact assignments and a trip logic that fired at the wrong moment. The breaker did not care. The process did. Always photograph the nameplate, terminal labels, and any plug-in module positions before removal.
Installation & Configuration Guide
- Pre-Installation ️
- Obtain a work permit and confirm the protection scheme is in a safe state.
- Verify whether the relay is tied to trip, block, or alarm functions.
- Photograph the existing nameplate, terminal wiring, and any plug-in settings.
- Removal
- Label every wire before disconnecting.
- Remove terminal screws or plug connectors carefully.
- Release mounting hardware and withdraw the relay.
- Installation
- Match the full suffix exactly: MVTU11K1CD0751G, not just “MVTU11.”
- Mount securely and reconnect wiring per the labels.
- Double-check AC voltage input, trip outputs, and interlock contacts.
- Power-On & Testing
- Apply auxiliary supply and confirm normal indication.
- Verify no false trip on energization.
- If permitted, perform a supervised undervoltage function test.
- Record the new relay serial number, suffix code, and test results in the maintenance log.
Compatible Replacement Models
| Compatibility | Model | Notes |
|---|---|---|
| Drop-in Replacement | ALSTHOM/GE MVTU11K1CD0751G | Same full model and suffix; confirm nameplate and contact configuration |
| ️ Engineering Review Required | ALSTHOM/GE MVUA11 / MVTU11 variants | Same family, but suffix, voltage rating, and contact set may differ |
| ️ System-Level Upgrade | GE Vernova PRiMA relay family | GE Vernova lists PRiMA as the alternative for discontinued MVUA relays; requires wiring and logic review |
| Not Compatible | Generic PLC digital output modules | Cannot replace a dedicated undervoltage protection relay without full scheme redesign |
| Not Compatible | MVAX/MVAJ trip supervision relays | Different function; trip circuit supervision is not undervoltage protection |
Frequently Asked Questions (FAQ)
Q: Can I replace any MVTU11 relay with MVTU11K1CD0751G?
No. The suffix code matters. Check the AC voltage rating, contact configuration, delay setting, and logic sequencing against the existing unit and OEM documentation.Q: Is this still in production?
No. The MVUA/MVTU11 family is a legacy ALSTHOM/GE product. GE Vernova has discontinued manufacturing and points to PRiMA relays as the alternative.Q: What does this relay actually protect against?
It monitors AC supply voltage and trips or blocks after a set delay when voltage falls below the configured threshold. It is not a trip-circuit monitor and not a general-purpose PLC.Q: Can I hot-swap this relay?
Only if site procedures allow it and the protection scheme remains secure during replacement. In most protection panels, I would not assume hot-swap is acceptable without written approval.Q: What should I document before removal?
Nameplate photo, full suffix code, serial number, wiring labels, delay settings, logic state configuration, and test results. Protection auditors will ask for these.Q: Can a modern PRiMA relay replace this directly?
Not automatically. PRiMA is the GE Vernova successor direction for discontinued MVUA relays, but contact mapping, voltage inputs, and logic behavior must be verified before substitution.