Key Technical Specifications
- Input voltage: 85–264 VAC, 90–350 VDC
- Output configuration: Two independent, isolated outputs
- Output voltage: 24.7 VDC per channel
- Output current: 5 A per channel
- Total output power: Approximately 247 W
- Efficiency: Up to about 89%
- Isolation voltage: 2.8 kVDC
- Protection: Overload, short-circuit, overvoltage, overtemperature, input UV/OV lockout
- Mounting: 35 mm DIN rail
- Cooling: Convection / natural air cooling
- Operating temperature: -40°C to +60°C for LW models
- Standards: UL 508 listed; TÜV/CSA/Nemko approvals reported; EMC to EN 55011/55032 and EN 61000-3-2; railway variants reference EN 50155/50121
Product Introduction
I’ve replaced enough burnt DIN rail supplies to respect the ones that don’t need forced air cooling. The Bel Power LWN2660-6 is a dual-output 24.7 VDC industrial power supply built for control cabinets, instrumentation racks, outdoor enclosures, and harsh AC/DC-fed systems. It sits on a 35 mm DIN rail and delivers two isolated outputs, which matters when you’re feeding separate control buses, sensors, relays, or small DC drives from one brick.What makes it useful in the field is the wide input range and the dual regulated outputs. It accepts 85–264 VAC or 90–350 VDC, so it can tolerate unstable mains or DC-fed installations without immediately dropping out. Each output delivers 24.7 VDC at 5 A, with short-term peak power capability for inrush-heavy loads. The conformal-coated PCB, isolated outputs, and wide operating temperature range are why I’ve seen these survive panels that bake in summer. Just remember: the plain “-6” revision is old. If you’re replacing it, push for the E or EW suffix unless the existing wiring and EMC setup are already locked in.
Quality SOP & Tech Pitfalls
The Lab Report (SOP):
Every unit gets a visual counterfeit check first. I look for mismatched labels, reprinted stickers, corroded terminals, or fresh solder on a supposedly used part. Then it goes on a bench supply: low-line, nominal, and high-line AC input checks, followed by DC input verification if the variant supports it. I measure both 24.7 VDC outputs under no load, half load, and full load, check ripple, verify isolation, and confirm the green LED status. Final step is thermal soak, terminal torque check, and anti-static bagging with the firmware/revision label photographed.The Engineer’s Warning (Pitfalls):
Do not treat LWN2660-6, LWN2660-6E, and LWN2660-6EG as identical. The E suffix means improved EMC performance, and the non-E version is obsolete. I once swapped a plain “-6” into a panel that had been running an E-revision; it powered up fine, but nearby analog signals got noisy because the older unit had different filtering. Another common mistake is ignoring the system connector option. Some variants use a front connector for remote sense, auxiliary signals, or output adjustment. Plug the wrong option in, and you’ll chase a “bad supply” problem that’s actually a missing sense link.
Installation & Configuration Guide
- Pre-Installation: Shut down the control circuit. Verify zero voltage on AC input terminals. Wait for capacitors to discharge. Photograph the old unit’s label, wiring, DIP/option settings, and system connector pinout. ️
- Removal: Label every wire. Release the DIN rail clip carefully. Disconnect AC input, DC outputs, and any system connector. Check terminal screws for heat discoloration.
- Installation: Confirm the replacement suffix matches the original. If the old unit had remote sense or auxiliary options, copy the connector wiring exactly. Seat the DIN rail clip firmly; a half-latched supply vibrates loose.
- Power-On & Testing: Apply AC input. Verify both outputs read close to 24.7 VDC. Check LED status. Load each output separately, then together. Confirm no abnormal heating, buzzing, or voltage droop after a short run-in period.
Compatible Replacement Models
| Compatibility | Model | Notes |
|---|---|---|
| Drop-in | LWN2660-6E | Same dual 24.7 VDC output family; improved EMC. Verify option codes before swapping. |
| Drop-in | LWN2660-6EG | RoHS-compliant variant in the same family. Check system connector and temperature suffix. |
| ️ Software/Config Compatible | LWN2660-6E / EW series with matching option codes | Hardware is compatible, but option suffixes for connectors, temp range, and EMC must match. |
| Hardware Mod Required | Single-output LWN variants or different voltage ratings | Output voltage, power rating, or connector layout may differ. Not a direct swap. |
Frequently Asked Questions (FAQ)
Can I replace LWN2660-6 with LWN2660-6E?
Usually yes. The E version is the improved EMC revision of the same family. Still verify the option suffix, connector type, and temperature rating before wiring it in.Is LWN2660-6 still in production?
The base LWN2660-6 is considered obsolete. New designs and most replacements should target the E or EW suffix versions.Can it run on DC input?
Yes. The family supports wide-range DC input in addition to AC. Confirm the exact variant label before applying DC.What happens if one output is lightly loaded?
The two outputs are independently regulated, but cross-load regulation still depends on the specific variant and wiring. If your loads are sensitive, use remote sense if the option is available.Does it need a fan?
No. It is convection-cooled. That’s good for dusty panels, but you still need clearance around the unit so heat can escape.Is it safe for outdoor cabinets?
It’s built for demanding environments and has conformal-coated PCBs, but it is not a waterproof enclosure. The cabinet IP rating still matters.What should I check before accepting a used unit?
Label match, option suffix, terminal condition, burn marks, output voltage under load, and LED behavior. If the seller can’t show a loaded test, treat it as unverified.