Key Technical Specifications
| Parameter | Specification |
|---|---|
| Product Model | LSU-112DG |
| Manufacturer | DEIF |
| Product Type | Load Sharing Unit |
| Application | Diesel and gas generator control, standalone and parallel operation |
| Control Modes | Frequency control in standalone mode; frequency and power control in parallel mode |
| Governor Interface | Electronic potentiometer, e.g., EPQ96-2 or EPN-110DN |
| Built-in Functions | Power and frequency transducers for external device connection |
| Operating Modes | Fixed-power mode and isochronous mode supported |
| Speed Control | Two relays |
| System Compatibility | DEIF LSU-series generator control systems |
| Mounting | Panel-mounted industrial module (verify exact dimensions with physical unit) |
| Power Supply | Confirm rated supply voltage on nameplate before installation |
| Hot-Swap | Not confirmed; treat as non-hot-swappable unless OEM documentation states otherwise |
Product Introduction
The DEIF LSU-112DG is one of those modules that does not try to be a full generator controller, but it does one job very well: keeping generators sharing load properly when they run in parallel. It sits between the generator control system and the governor, using an electronic potentiometer to adjust speed and power output so that multiple units stay balanced.In the field, you usually see LSU units on older diesel or gas generator sets where the main controller handles protection and sequencing, while the LSU handles load sharing and frequency droop behavior. It is simple, purpose-built, and generally reliable if the governor interface is wired correctly. The main risk is not the module itself, but mismatched configuration. If the droop setting, potentiometer type, or relay assignment does not match the governor, the unit may hunt, refuse to share load, or push one generator into motoring.
Quality SOP & Tech Pitfalls
The Lab Report (SOP)
- Visual inspection: verify DEIF labeling, model LSU-112DG, serial number, and terminal condition.
- Connector check: inspect governor interface terminals, potentiometer connections, and power supply terminals.
- Power-up test: apply rated supply and confirm basic LED or indicator response if equipped.
- Signal verification: check power and frequency transducer outputs against known references when test equipment is available.
- Relay function check: verify speed-control relay operation and contact integrity.
- Final packing: clean, anti-static bag, foam protection, and secure shipping.
The Engineer’s Warning (Pitfalls)
- Do not confuse LSU-112DG with a full genset controller. It is a load sharing unit, not a replacement for a complete generator protection or automation controller.
- Governor compatibility matters. The LSU-112DG expects a compatible electronic potentiometer interface. If the governor uses a different actuator type, additional interfacing may be required.
- Parallel tuning is not optional. Droop settings, CT polarity, and power signal scaling must be checked before loading the generator set.
- Do not assume isochronous mode is safe on every system. Isochronous operation can cause instability if more than one unit is set to isochronous without proper master/slave coordination.
Installation & Configuration Guide
- Pre-Installation
- Confirm the generator set is isolated and control power is safe to work on.
- Photograph existing wiring, potentiometer connections, and LSU terminal labels.
- Verify the replacement LSU-112DG matches the original application.
- Removal
- Label all wiring before disconnection.
- Remove terminal connections carefully.
- Release mounting hardware and remove the module.
- Installation
- Mount the replacement LSU-112DG securely.
- Reconnect power, governor interface, potentiometer, and measurement inputs.
- Verify CT polarity and power signal wiring if used for load sharing.
- Commissioning
- Apply control power and verify normal indication.
- Test standalone frequency control before parallel operation.
- Perform load sharing tests with the other generator set(s).
- Adjust droop, gain, and stability settings as required by site procedure.
Compatible Replacement Models
| Model | Compatibility | Notes |
|---|---|---|
| DEIF LSU-112DG (same revision) | Drop-in replacement | Preferred option if labeling and application match. |
| DEIF LSU-113DG / LSU-114DG | Review required | Related LSU family members, but functions and terminals may differ. |
| Non-DEIF load sharing units | System-dependent | May work only if governor interface and signal scaling are compatible. |
| Full generator controllers | Not a direct substitute | A full controller may offer more functions but requires system re-engineering. |
Frequently Asked Questions (FAQ)
What does the LSU-112DG do?
It provides load sharing and frequency/power control for diesel and gas generators, typically by interfacing with the governor through an electronic potentiometer.Can it run generators in parallel?
Yes. It supports parallel operation with other generator sets, provided droop, CTs, and governor settings are correctly configured.Is it a full generator controller?
No. It is a load sharing unit. Protection, sequencing, and full automation usually remain with the main generator controller.Can it run in isochronous mode?
The LSU-112DG supports isochronous and fixed-power modes, but isochronous operation must be applied carefully in multi-unit systems to avoid instability.What governor interfaces does it support?
It is typically used with DEIF electronic potentiometers such as EPQ96-2 or EPN-110DN. For other governors, the interface must be verified.Do you provide test documentation?
Photos, label details, and basic functional test records can be provided when available. Site commissioning and parallel testing should still follow local procedures.