Key Technical Specifications
| Parameter | Value |
|---|---|
| Product ID | 892042336 |
| Software Version | V5.6 Build 1501.9810 IV1 |
| Hardware Key | USB Hardlock (Required) |
| Target Hardware | HIQuad H41q / H51q Series |
| Supported CPUs | F8650E, F8652E, F8621A, F8650X |
| Programming Standard | IEC 61131-3 (FBD, SFC) |
| Safety Certification | TÜV SIL3 (IEC 61508/61511) |
| OS Compatibility | Windows 7 / 10 / Server 2016+ |
| Communication | SafeEthernet, Serial |
| Language | English Standard (IV1) |
Product Introduction
HIMA ELOP II 892042336 Version V5.6 serves as the dedicated engineering environment for configuring and maintaining HIQuad safety instrumented systems. This software package, secured by a physical USB hardware key, enables engineers to program SIL3 safety logic and perform online diagnostics.Integrators must distinguish this release from the newer ELOP II Factory; V5.6 is strictly for legacy H41q and H51q controllers. (I’ve seen too many sites order the wrong toolchain, only to realize they can’t talk to their older F8650E CPUs.)
Installation & Configuration Guide
Preparation (10 min)
- Verify Windows OS meets V5.6 system requirements.
- Locate the USB Hardlock (892042336); software will not run without it.
- Temporarily disable antivirus software to prevent driver blocking.
Removal (5–10 min)
- Stop any running ELOP II background services.
- Backup existing project files (.eii) to external storage.
- Uninstall previous version via Windows Control Panel.
Installation (10 min)
- Insert USB Hardlock before running Setup.exe.
- Run installer as Administrator; follow prompts for typical install.
- Reboot system when prompted to finalize driver installation.
Power-On & Test (10 min)
- Launch ELOP II Professional; verify license status is “Valid”.
- Create a test project; select HIQuad H41q hardware configuration.
- Connect to controller via SafeEthernet; perform online scan.
- (If the dongle isn’t recognized, try a different USB port — I’ve had issues with USB 3.0 hubs causing handshake failures.)
Troubleshooting Quick Reference
| Symptom | Probable Cause | Corrective Action |
|---|---|---|
| License Error | Dongle Not Detected | Re-seat USB; check Device Manager for Hardlock. |
| Cannot Connect | Firewall Blocking | Allow ELOP II through Windows Firewall. |
| Build Failed | Version Mismatch | Ensure project hardware matches V5.6 library. |
| Crash on Startup | Corrupt Config File | Delete user config in AppData; restart software. |
| Download Failed | CPU Busy/Protected | Check CPU mode; clear safety lockout if authorized. |
Dimensions, Mounting & Wiring Notes
- Form Factor: Software Media + USB Hardware Dongle.
- Mounting: N/A (Workstation Installation).
- Storage: Keep USB Hardlock in anti-static bag when not in use.
- Network Note: Use dedicated engineering VLAN for controller communication.
- Compatibility Warning: Do not install on machines running ELOP II Factory V8+ to avoid registry conflicts.
FAQ
Can I use this dongle on multiple computers?
No. The Hardlock is a single-node license. For concurrent use, you need a network license server setup.I lost the USB key; can I buy just a replacement?
No. The dongle contains the encrypted license. You must purchase a full replacement kit (892042336) and provide proof of ownership for re-authorization.Is V5.6 compatible with HIMatrix systems?
No. HIMatrix requires ELOP II Factory V8.0 or higher. This version is exclusively for HIQuad H41q/H51q hardware.Why does my antivirus flag the installer?
The installer modifies system drivers for hardware communication. Whitelist the ELOP II installation directory and re-run.Can I upgrade from V5.5 to V5.6 directly?
Yes, V5.6 is a direct upgrade path. However, always backup your projects before upgrading, as database schema changes may occur.Does this support remote access?
Yes, via TCP/IP. Ensure your network security policy allows remote engineering access to the safety controller.Where can I find the SIL3 certification documents?
They are included in the /Documentation/Certificates folder on the installation media. Always verify the certificate matches your specific application requirements.