Description
Key Technical Specifications
| Parameter | Specification |
|---|---|
| Processor | High-speed Intel Celeron-M microprocessor |
| User Memory | Expanded RAM (with reserved blocks for discrete and analog I/O) |
| Flash Storage | Substantial NVRAM for program and fixed data retention |
| Program Blocks | Supports multiple program blocks with extended block size limits |
| I/O Capacity | High-density discrete and analog I/O point support |
| Processing Speed | High-speed I/O operations per second |
| Serial Ports | Dedicated RS-232 and RS-485 ports (supports SNP, Serial I/O, Modbus RTU) |
| Ethernet | 10/100 Mbps port (supports TCP/IP, EtherNet/IP, Modbus TCP) |
| Power Supply | 24 VDC (with specified max current draw) |
| Operating Temp | Standard and extended industrial temperature ranges |
| Programming | Proficy Machine Edition (LD, FBD, ST, C) |
Product Introduction
You don’t drop a PACSystems RX3i CPU into a control panel unless you expect the plant floor to get hammered. The GE IC695CPU315-CD is built for those heavy-duty process control and material handling systems where a standard PLC would choke on the data load. I’ve used this exact model to replace aging Series 90-30 processors, and the raw execution speed on the high-speed Celeron-M is noticeably faster when you’re pushing heavy floating-point math or managing high-speed serial traffic. It doesn’t just scan ladder logic; it actively crunches complex data without blowing past your watchdog timer.What actually makes this specific revision a staple in my spares inventory is the expanded user RAM paired with substantial flash storage. That memory footprint gives you the breathing room to map out thousands of tags and store massive data logs locally without constantly paging out to a SCADA server. It talks to legacy Series 90-30 I/O racks just as happily as it talks to modern distributed Ethernet blocks. Just a heads-up: this CPU is notoriously picky about its backplane termination. If you don’t seat the bus terminator correctly, you’ll spend your weekend chasing ghost communication faults.
Quality SOP & Tech Pitfalls
The Lab Report (SOP)
Before this module leaves my bench, it survives a specific gauntlet.
- Visual & Counterfeit Check: I inspect the PCB traces for micro-fractures and verify the silkscreen against known GE OEM standards.
- Live Test: Mounted on a test rack, I boot the firmware and verify the processor clock speed and memory allocation via Proficy Machine Edition.
- Electrical Checks: Using a Fluke multimeter, I verify the 24 VDC input tolerance and check for shorts across the RS-485 termination resistors.
- Firmware Logging: I document the exact firmware revision. You cannot mix and match CPU revisions blindly if you’re running a redundant pair.
- Sealing: Anti-static bag, desiccant pack, and heavy-duty corrugated box.
The Engineer’s Warning (Pitfalls)
The number one killer of these modules isn’t a power surge; it’s a dead backup battery. The IC695CPU315-CD relies on an external smart auxiliary battery (like the IC695ACC302) to hold its volatile RAM during a power loss. I once got called to a water treatment plant where the client experienced a total blackout. When power returned, the CPU came up in a fault state with a blank memory. The maintenance manager swore the battery was “checked last year.” I tested it; the voltage was right on the edge. It held just enough charge to keep the CPU happy while powered on, but collapsed the second the grid dropped. We replaced the battery, reloaded the logic, and I made them put a quarterly battery voltage check in their PM schedule.Another trap: Backplane bus termination. This CPU uses a dual backplane bus to talk to I/O and intelligent option modules. If you are swapping this into an existing rack and you fail to install the bus terminator plug in the final slot, the CPU will flag a bus fault and halt.
Installation & Configuration Guide
Phase 1: Pre-Installation
- ️ Lockout/Tagout: Isolate the 24 VDC power to the specific rack.
- ️ Discharge: Wait for internal capacitors to bleed off completely.
- ️ Documentation: Photograph the existing wiring, paying extreme attention to the RS-232/RS-485 pinouts and the Ethernet subnet configuration.
Phase 2: Removal
- Label every single serial and Ethernet cable. Do not rely on memory.
- Disconnect the backplane connectors carefully.
- Release the rack mounting clips. Support the chassis while pulling it straight out to avoid bending the backplane pins.
Phase 3: Installation
- Mount the new IC695CPU315-CD securely into the designated CPU slot.
- Verify Battery Connection: Ensure the smart auxiliary battery is firmly connected and seated.
- Check Termination: Confirm the bus terminator plug is installed in the last slot of the rack.
- Seat the backplane connectors firmly. A loose connection here will cause the module to flag a “Bus Fault” and zero out the data.
Phase 4: Power-On & Testing
- Restore 24 VDC power. Watch the front-panel LEDs. You want a solid green “OK” status.
- Open Proficy Machine Edition. Verify the CPU is communicating over the Ethernet port.
- Download your logic. If you see erratic I/O readings, check your backplane bus termination immediately.
Compatible Replacement Models
- Drop-in Replacement: IC695CPU315 (Same Firmware)
Full hardware and software match. If you are swapping a failed unit, ensure the firmware version matches your existing Proficy configuration, or you will spend hours recompiling the logic. - ️ Software Compatible: IC695CPE330
Same physical form factor, but this is an Ethernet-only CPU. You will lose the physical RS-232/RS-485 ports, requiring you to use external serial-to-Ethernet gateways. Expect several hours of engineering labor to remap your serial drivers. - Hardware Mod Required: IC693CPU364
This is a legacy Series 90-30 CPU. It uses a completely different backplane architecture, memory model, and programming environment. Do not attempt this swap unless you are doing a full system redesign and replacing the entire rack.
Frequently Asked Questions (FAQ)
Can I hot-swap this module while the plant is running?
Technically, the RX3i hardware supports it. But practically? I don’t recommend it unless you have a redundant CPU pair. Yanking the primary CPU drops your control logic for the duration of the swap. If a real fault happens during those minutes, you’re flying blind.Why is the CPU showing a “Battery Low” fault?
The user RAM is volatile. The CPU constantly monitors the voltage of the smart auxiliary battery. If that voltage drops below the threshold, it flags a fault. Use your multimeter to check the battery terminals. Replace it immediately with an IC695ACC302 or equivalent.Does this CPU support redundant configurations?
Yes, but it requires specific hardware. You need a matched pair of CPUs and the dedicated redundancy modules. It is not a simple plug-and-play operation; the logic must be compiled specifically for a high-availability environment.What happens if I lose my Ethernet connection to the SCADA system?
The CPU keeps running. It will continue to scan its ladder logic, process the I/O, and update its internal memory. However, you will lose remote visibility in Proficy, and any Modbus TCP polling from your HMI will time out. The local control logic remains fully active.Can I use Series 90-30 I/O modules with this CPU?
Yes, the IC695CPU315-CD supports most legacy GE Fanuc Series 90-30 modules and expansion racks. However, you must ensure the backplane bus termination is correct, or the CPU will not recognize the legacy blocks.Is the -CD suffix a special version?
The -CD suffix generally denotes a specific hardware revision or regional compliance variant. Electrically and functionally, it operates identically to the base IC695CPU315. Always verify the exact revision against your OEM documentation before ordering.