Key Technical Specifications
| Parameter | Specification |
|---|---|
| Manufacturer | Lantronix |
| Part Number | 080-332-000-R |
| Product Line | XPress DR+ Series |
| Network Interface | 10Base-T/100Base-TX Ethernet (RJ45) |
| Serial Interface | Configurable RS-232, RS-422, or RS-485 |
| Isolation | 2000V serial isolation, 1500V Ethernet isolation |
| Power Input | 9-30VDC or 9-24VAC |
| Operating Temp | 0°C to 60°C (32°F to 140°F) |
| Mounting | DIN-rail enclosure |
| Configuration | Web Manager, Telnet, DeviceInstaller™ software |
| Compliance | RoHS compliant |
Product Introduction
When you’re dealing with a retrofit on an older packaging line or a remote water treatment site, replacing every piece of legacy serial equipment isn’t in the budget. That’s exactly where the Lantronix 080-332-000-R earns its keep. It’s an XPress DR+ series device server that takes serial data, encapsulates it, and shoots it over Ethernet. You get a virtual serial link. I’ve deployed these to connect plant-floor PLCs and weighing scales to MES systems without touching the core control network topology.Engineers don’t buy this thing for bells and whistles; we buy it because it doesn’t drop packets when the VFDs spin up. The galvanic isolation is the real story here—2000V on the serial side and 1500V on the Ethernet side. That keeps ground loops from frying the comms port when you’re tying disparate systems together. It runs on a wide 9-30VDC input, which is a lifesaver when your 24VDC plant supply dips under heavy load. Side note: The IAP (Installable Application Processor) version of this series supports downloadable industrial protocols, but verify your exact firmware revision before assuming you can load custom protocol drivers.
Quality SOP & Tech Pitfalls
The Lab Report (SOP):
Before anything leaves our dock, it goes through a rigorous gauntlet.
- Visual & Counterfeit Check: Inspecting the DIN-rail chassis, RJ45 jacks, and terminal blocks for oxidation or aftermarket tampering.
- Live Test on Rack: We power it up, assign a static IP via DeviceInstaller, and pass continuous ASCII data through the serial port to verify zero packet loss over a 2-hour burn-in.
- Insulation & Multimeter Checks: Using a Fluke 115 to verify the 2000V isolation barrier integrity and confirm terminal continuity.
- Firmware Logging: We flash it to the latest stable OEM firmware (or match your specific legacy version if requested) and log the build number.
- Anti-Static Sealing: Bagged with desiccant and ESD shielding.
The Engineer’s Warning (Pitfalls):
Don’t just slap this in and expect it to work out of the box. The out-of-the-box IP settings and serial parameters (baud rate, parity, stop bits) rarely match your legacy device. I once watched a junior tech waste three hours chasing a “bad module” because he didn’t set the serial port to match the RS-485 2-wire vs. 4-wire configuration of the field device. The module was fine; the jumper and software settings were wrong.Another massive headache? Grounding. Even with the internal isolation, if you’re running long RS-485 runs, you must terminate the line properly at the physical ends. Skip the termination resistors, and you’ll get signal reflections that corrupt your Modbus RTU frames.
Installation & Configuration Guide
Phase 1: Pre-Installation
⚠️ Safety First: Lock out/tag out the power to the legacy serial device. Wait for capacitors to discharge.
⚠️ Document Everything: Photograph the old wiring, terminal assignments, and any existing DIP switch or jumper block configurations. If you are replacing a failed unit, you must know exactly how the old one was wired.Phase 2: Removal & Mounting
Snap the new 080-332-000-R onto a clean DIN rail. Leave at least an inch of clearance on the sides for heat dissipation—these run warm in a packed control panel. Label every wire before you pull it from the old unit.Phase 3: Wiring & Jumper Configuration
This is where 90% of startup failures happen.
- Power: Connect 9-30VDC to the power terminals. Observe polarity.
- Serial: Wire your RS-232/422/485 lines. If using RS-485, ensure you know if your specific sub-model requires internal termination jumpers to be enabled.
- Ethernet: Cat5e/6 cable to your switch.
Phase 4: Power-On & Testing
Apply power. Watch the LED status indicators. The ACT (Activity) and LINK lights should illuminate. Use Lantronix DeviceInstaller software on your laptop to find the module’s MAC address and assign a static IP. Open a Telnet session or use the Web Manager to configure the serial port parameters (baud, data bits, parity) to exactly match your legacy device. Test the data flow.
Compatible Replacement Models
| Compatibility Tier | Model / Option | Notes |
|---|---|---|
| ✅ Drop-in Replacement | 080-332-000-R (New Surplus/Refurb) | 100% hardware match. Requires IP and serial parameter configuration, but wiring remains identical. |
| ⚠️ Software Compatible | Lantronix EDS1000 / EDS2000 Series | Newer generation. Hardware is similar, but requires firmware flash and complete reconfiguration via new web interface. Expect 1-2 hours of engineering labor. |
| ❌ Hardware Mod Required | Moxa NPort / Advantech EKI Series | Different terminal block layouts, different mounting dimensions, and proprietary configuration software. Requires panel modification and complete rewiring. Avoid unless doing a full panel rebuild. |
Frequently Asked Questions (FAQ)
Can I hot-swap this safely?
No. While the Ethernet side might tolerate it, yanking the 24VDC power or messing with the RS-485 terminals while the system is live is a great way to induce a voltage spike and fry the serial port of your connected PLC or HMI. Kill the power, swap the module, restore power.My old module died. Will the new one just work?
Only if you configure it. These modules hold their IP address and serial settings in non-volatile flash memory. A new unit comes with factory defaults. You will need to use DeviceInstaller to assign the correct static IP and match the baud rate/parity of your legacy equipment. If you didn’t photograph the old wiring, you’ll be guessing on the RS-485 2-wire vs 4-wire pinout.Does this support Modbus TCP to Modbus RTU conversion?
The standard XPress DR+ acts as a transparent “pipe”—it passes raw serial data over TCP/IP. If your SCADA system expects a Modbus TCP gateway, you might need the IAP (Installable Application Processor) version, or you’ll need to run a mapping software (like Com Port Redirector) on a host PC to handle the protocol translation. Check your specific firmware capabilities.What happens if the Ethernet network goes down? Does it lose serial data?
The module has a small internal buffer. If the network drops, it will hold a limited amount of incoming serial data. However, if the outage lasts longer than the buffer capacity, data will be overwritten and lost. It is not a data logger. Ensure your network switch is reliable.Is the 0-60°C operating temperature rating enough for a hot plant floor?
In a climate-controlled panel, yes. But if your panel is sitting next to a boiler or in direct sunlight in July, the internal ambient temp can easily exceed 60°C. I always recommend adding a panel exhaust fan or a thermostat-controlled AC unit if you’re mounting these in a harsh environment. Heat kills electrolytic capacitors.Do you provide a warranty on the New Surplus units?
Yes. We stand behind our testing. If it fails out of the box or during the warranty period due to a manufacturing defect (not lightning strikes or reverse polarity), we replace it. We test every unit on a live rack before shipping, so DOA rates are practically zero.