Key Technical Specifications
- Model: IC695ACC412-AA
- Function: Power supply module for PACSystems RX3i rack
- Mounting: Single-slot, rack/backplane mounted
- Input: Rack backplane / field supply — confirm voltage class on the OEM datasheet
- Outputs: Backplane power to CPU and I/O modules
- Indicators: Status LEDs (module health, output state)
- Configuration: No DIP switches; software-configured into the PLC system
- Environment: 0–60 °C operating, 5–95% RH non-condensing (typical for the IC695 family)
- Compliance: UL / CSA / FCC (typical for the series)
Product Introduction
A dead power supply takes down the whole rack — CPU, I/O, comms, everything. Not just one channel. That is why I keep an IC695ACC412-AA on the shelf even though the platform is long past its prime.This is a GE Fanuc PACSystems RX3i rack power supply. It sits in a single slot, feeds the backplane, and carries the rack when the incoming supply misbehaves. There is no DIP switch to set and no firmware to flash — you install it, the CPU sees it, and it either powers the rack or it doesn’t. Simple parts fail quietly, and that is the problem.Engineers buy it because the alternative is a fabrication. The RX3i line is discontinued; a failed supply in a 2004-vintage rack means hunting the aftermarket for a working unit. One honest caveat: the reseller data on this part number is a mess. I’ve seen it listed as a “cap pack module” and as a “bus interface module” by different sellers. It is a power supply. Trust the nameplate, not the listing.
Quality SOP & Tech Pitfalls
The Lab ReportEvery unit gets the same treatment. Visual and counterfeit check first — I look at label print quality, solder joints on the backplane connector, and capacitor tops for bulging. Then a live test: mounted in a test rack, input energized, backplane voltage measured with a Fluke 115 at the CPU slot and at the far end of the rack. Output ripple checked. Insulation resistance measured field-to-backplane. LED states logged and photographed. Anti-static bag, foam, sealed box. Test photos and meter readings available on request.The Engineer’s WarningTwo things burn people on this part.First: assuming any IC695 power supply is interchangeable. The IC695 family has several supply variants with different current ratings. Install a lower-rated unit and the rack powers up fine — until you add a sixth I/O module, then it browns out intermittently under load. Count your modules and check the current budget before you buy.Second: not photographing the old unit. There are no DIP switches here, but the slot position and the backplane connector orientation matter. I once watched a tech install a replacement in the wrong slot because he “remembered” it. The rack didn’t power up, and he blamed the part for two hours.Field disaster, real one: a maintenance tech replaced a failed supply during a night shift, didn’t verify the output voltage at the CPU slot, and walked away. The supply was current-limited. The CPU ran for six hours, then dropped. Six hours of process data gone.
Installation & Configuration Guide
Phase 1 — Pre-Installation (⚠️)
- ⚠️ Notify the control room. Confirm this is a planned outage — this is not a hot-swap part in most configurations.
- ⚠️ Photograph the old module’s nameplate: model, serial, slot position.
- ⚠️ Record the rack’s module count and total current draw.
- Shut down the rack. Wait 60 seconds for bulk capacitors to discharge.
Phase 2 — Removal
- Label the field power leads before disconnecting.
- Release the module’s retaining clips. Do not pull by the wires.
- Extract straight out. Note the connector orientation.
Phase 3 — Installation
- Verify the replacement’s model and current rating match the removed unit exactly.
- Seat the module fully into the backplane connector. Hand tight on the clips.
- Reconnect the field power leads to the same terminals. Polarity matters — reverse polarity kills the module.
Phase 4 — Power-On & Testing
- Energize. Confirm the module LED indicates healthy.
- Measure backplane voltage at the CPU slot with a Fluke 115. Compare to the OEM spec.
- Confirm the CPU boots and the I/O modules come online.
- Log the readings. Keep the old module for teardown or RMA.
Compatible Replacement Models
- ✅ Drop-in: IC695ACC412-AA (same part). Only true match. Buy one spare — this is an obsolete part.
- ⚠️ Software Compatible: IC695ACC412 (base suffix). Same hardware, different revision code. Verify the current rating and slot compatibility before installing.
- ❌ Hardware Mod Required: Other IC695 power supplies (e.g., IC695PSA140). Different form factor or rating. Requires re-engineering the rack power budget. Not advised unless you are doing a full rack upgrade.
Frequently Asked Questions
Is this part still available new from GE?
No. The RX3i line is discontinued. What you find is New Surplus or New Old Stock. I photograph the actual nameplate before shipping so you can verify the revision yourself.Can I hot-swap it?
Generally no. Unlike I/O modules, the power supply feeds the whole rack. Removing it drops the CPU. Plan an outage.The rack powers up but the CPU faults after a few hours. Is it the supply?
Probably. That is the classic current-limited symptom. Measure the backplane voltage at the CPU slot under load, not at idle. If it sags more than the spec allows, the supply is marginal.Will an IC695ACC412 (no suffix) work?
Likely yes, but confirm the current rating on the nameplate. Suffix revisions sometimes change the rating.What condition do you ship in?
New Surplus / New Old Stock, tested on a live rack before shipping. Test photos and meter readings included.What is the warranty?
One year from delivery on functional failure. Does not cover reverse-polarity installation or over-current from an overloaded rack.Can you provide the test report?
Yes. Ask at quote stage and it ships with the unit.