Key Technical Specifications
| Parameter | Details |
|---|---|
| Order number | 200-582-915-032 |
| Product family | VM600 RPS6U power supply |
| System compatibility | VM600 / VM600 Mk2 19-inch 6U rack |
| Primary input | 24 V DC (verify exact input range on nameplate) |
| Internal outputs | +5 V DC and ±12 V DC to rack backplane and installed modules |
| Typical compatible racks | ABE040, ABE041, ABE042, ABE044, ABE056 |
| Module format | 6U VME-style rack module |
| Hot-swap support | Power modules are typically hot-swappable; confirm with OEM manual |
| Protection features | Overvoltage, overcurrent, reverse polarity protection typical for RPS6U family |
| Application | Powering MPC4, IOC4T, XMV16, XIO16T, CMC16, CPUM and related VM600 cards |
| Status | Discontinued / surplus; verify revision against installed rack |
| Documentation | Confirm with VIBRO-METER VM600 / RPS6U datasheet before final integration |
Product Introduction
VIBRO-METER 200-582-915-032 is a VM600 RPS6U-series 24 V DC power supply used in VM600 and VM600 Mk2 machinery protection racks. It converts external 24 V DC into regulated internal rails, typically +5 V DC and ±12 V DC, for backplane distribution to monitoring, protection and communication modules.This module does not process vibration signals itself. It keeps the rack alive. In field service, RPS6U failures usually show up as multiple cards losing status LEDs at once, relay chatter, CPUM communication loss, or intermittent MPC4/IOC4T faults. Because VM600 RPS6U units exist in several hardware revisions, the last three digits in the part number matter. Always match the installed revision or confirm cross-compatibility with the OEM datasheet before replacement.
Installation & Configuration Guide
Preparation (10 min)
- Record rack model, slot location and existing RPS6U part number.
- Photograph front label, rear connectors and adjacent module LEDs.
- Confirm external 24 V DC supply is stable and within nameplate limits.
- Prepare ESD strap, insulated tools and a multimeter.
Removal (5–10 min)
- Notify operations if the rack has no redundant power supply.
- Label external 24 V DC wiring before disconnecting.
- Release mounting hardware and slide the module out without forcing the backplane connector.
- Inspect backplane pins for bent contacts or carbon tracking.
Installation (10 min)
- Verify replacement part number 200-582-915-032 and hardware revision.
- Insert the module evenly until the backplane connector seats fully.
- Reconnect 24 V DC wiring with correct polarity.
- Secure mounting screws and confirm no loose terminals.
Power-On & Test (10 min)
- Measure incoming 24 V DC before enabling the supply.
- Power on and check RPS6U status LEDs.
- Verify +5 V DC and ±12 V DC rails if test points are accessible.
- Confirm MPC4, IOC4T, CPUM and relay cards return to normal status.
- Monitor the rack for 30 minutes under normal load.
Troubleshooting Quick Reference
| Symptom | Likely cause | First check |
|---|---|---|
| All cards dark | No input power or failed RPS6U | Measure 24 V DC at supply terminals |
| Intermittent rack reset | Loose backplane contact or failing capacitor | Reseat module; check for burnt smell near connectors |
| One module faulty, others OK | Module failure, not power supply | Swap suspect card; do not replace RPS6U yet |
| Relay chatter | Low internal rail voltage | Measure +5 V DC and ±12 V DC outputs |
| Replacement not recognized | Hardware revision mismatch | Compare nameplate revision with OEM documentation |
| Repeated trip after replacement | External 24 V DC fault or shorted backplane | Check upstream PSU, fuses and rack wiring |
Dimensions, Mounting & Wiring Notes
- Form factor: VM600 6U rack module, 19-inch system.
- Mounting: Front-access slide-in module with rear backplane connector.
- Orientation: Vertical rack mounting; maintain airflow around power module.
- Terminal notes: External 24 V DC wiring must match polarity markings; do not assume pinout from another RPS6U revision.
- Torque: Tighten terminal screws to OEM specification; loose power terminals cause intermittent faults faster than card failures.
- Exact H × W × D: Confirm from the VM600 RPS6U mechanical drawing, as revisions may vary.
FAQ
Can 200-582-915-032 replace other VM600 RPS6U modules?
Often yes, but not automatically. VM600 power supplies have revision-dependent compatibility. Match the installed revision or get written confirmation from the OEM datasheet.Is this a vibration monitoring card?
No. It is a rack power supply. It does not measure vibration, speed or temperature. It only powers the cards that do.What happens if I install the wrong revision?
The rack may power up but behave unpredictably. In some cases, internal rail tolerances, connector pinouts or protection thresholds differ. Always photograph the original nameplate before removal.Can it be hot-swapped?
VM600 RPS6U modules are generally designed for hot-swap in redundant configurations. Do not hot-swap a single power supply on a live protection rack without an approved procedure.Do you have this in stock?
Stock varies by revision. Lead time depends on whether the exact 200-582-915-032 revision is available. Send a nameplate photo for confirmation.I replaced the RPS6U but the MPC4 still shows a fault. What now?
Check the IOC4T pair, sensor loops, relay wiring and MPS configuration. A healthy power supply will not clear a configured alarm or a failed I/O card.