ABB REF601 CE446BB1NH | Feeder Protection Relay, 1 A CT, 4 BI / 6 BO, Modbus RTU

  • Model: REF601 CE446BB1NH
  • Brand: ABB
  • Series: Relion 605 series — REF601 feeder protection and control relay
  • Core Function: Protects and controls MV/LV feeders by measuring phase and ground currents, executing overcurrent/ground-fault logic, and operating the breaker with optional auto-reclose.
  • Type: Feeder Protection IED / Digital Overcurrent Relay
  • Key Specs: 1 A CT secondary inputs; 4 binary inputs + 6 binary outputs; Modbus RTU + IEC 60870-5-103 via RS-485; 24–265 V AC/DC auxiliary supply.
Category:

Description

Key Technical Specifications

Parameter Specification
Order Code REF601 CE446BB1NH
Standard IEC version
Application Configuration “E4” = 1 A phase + ground CT inputs
I/O Configuration “46” = 4 binary inputs + 6 binary outputs
Communication Modbus RTU + IEC 60870-5-103 via 2-wire RS-485
Auxiliary Supply 24–265 V AC/DC universal supply
CT Inputs 3 phase currents + 1 ground/residual current
Rated Secondary Current 1 A
Protection Functions 3-stage overcurrent, 2-stage ground fault, thermal overload, phase discontinuity, breaker failure, inrush stabilization, auto-reclose (up to 4 shots)
Breaker Control Local/remote trip-close with trip-circuit supervision
Mounting Press-fit panel mounting, compact half-rack form factor
Terminal Type Detachable wiring terminals with CT shorting facilities

 

Product Introduction

The REF601 CE446BB1NH is the kind of relay you find on older MV switchgear where someone needed a compact feeder protection unit that could still talk to SCADA without a full IEC 61850 upgrade. It sits in ABB’s Relion 605 family as a feeder protection and control relay, not just a plain overcurrent trip unit. The “CE446BB1NH” code tells the real story: IEC standard, 1 A CT inputs, 4 BI / 6 BO, Modbus RTU / IEC 60870-5-103 communication, and a universal 24–265 V AC/DC supply.Engineers keep these in service because the function set is predictable. You get three overcurrent stages, two ground-fault stages, thermal overload, phase discontinuity, breaker failure, and auto-reclose up to four shots. The 1 A CT input variant is useful on longer cable runs or where the existing instrument transformers were specified for 1 A secondary. It is not a modern IEC 61850 relay, but for many brown-panel replacements that is exactly why it still works.

Quality SOP & Tech Pitfalls

The Lab Report (SOP)

  • Visual inspection: verify order code label “REF601 CE446BB1NH,” serial number, housing damage, terminal block condition, and mounting clips.
  • Counterfeit/revision check: confirm ABB branding, label format, and firmware/version plate against OEM documentation.
  • Power-up test: apply 24–265 V AC/DC auxiliary supply and verify boot sequence, display, and LED indicators.
  • I/O test: check 4 binary inputs and 6 binary outputs with dry contacts; confirm trip/close outputs and IRF/alarm signals.
  • Communication test: verify Modbus RTU / IEC 60870-5-103 on RS-485, correct baud rate, device address, and register mapping.
  • Protection function spot-check: inject secondary current into phase/ground inputs and confirm pickup, timing, and trip output.
  • Settings backup: read and archive existing configuration before shipment.
  • Packaging: anti-static bag, rigid box, terminal covers fitted, cable glands protected.

The Engineer’s Warning (Pitfalls)

  • Do not confuse “E4” with “A4” or “D4.” E4 means 1 A CT secondary. If your CTs are 5 A, this unit will read low and may not trip correctly.
  • The “B” communication option is Modbus RTU / IEC 60870-5-103 on RS-485. It is not IEC 61850. If your SCADA expects IEC 61850 MMS/GOOSE, this relay will not plug in cleanly.
  • Auto-reclose settings are dangerous if copied blindly. A cable feeder should not be treated like an overhead line.
  • Press-fit mounting looks simple until the panel cutout is worn. Check panel thickness and clip engagement; a loose relay is a vibration failure waiting to happen.

 

Installation & Configuration Guide

  1. Pre-Installation
    • Obtain a switching permit and isolate the feeder.
    • Verify CT secondary circuits are shorted before opening any wiring. ⚠️
    • Photograph existing wiring, CT polarity, binary I/O assignments, communication terminals, and relay settings. ⚠️
  2. Removal
    • Label all CT, binary I/O, communication, and auxiliary supply wires.
    • Short CT secondaries with proper shorting blocks or test switches.
    • Release terminal blocks and remove the relay from the panel cutout.
  3. Installation
    • Confirm the new unit matches REF601 CE446BB1NH exactly.
    • Check panel cutout dimensions and press-fit clips.
    • Wire CTs with correct polarity; keep ground/zero-sequence CT routing consistent with the original design.
    • Connect RS-485 with correct polarity and termination if required.
  4. Power-On & Testing
    • Apply auxiliary supply and verify normal boot.
    • Restore CT circuits only after wiring is confirmed.
    • Check phase currents, ground current, and breaker position indication.
    • Perform secondary injection on overcurrent and ground-fault stages.
    • Test trip/close outputs, binary inputs, and SCADA communication.
    • Record final settings and keep a backup file.

Compatible Replacement Models

Compatibility Model / Option Notes
✅ Drop-in Replacement REF601 CE446BB1NH Same order code, same I/O, same communication, same 1 A CT input.
⚠️ Software / CT Compatible REF601 CA446BB1NH 3 sensor inputs + ground; different analog input type. Requires CT/sensor verification.
⚠️ CT Rating Change REF601 CD446BB1NH 5 A CT version. Use only if existing CT secondaries are 5 A.
⚠️ Application Dependent REF615 / REJ615 Newer Relion family. Requires setting migration, I/O mapping, and SCADA integration work.
❌ Not a Direct Swap REM601 / RET615 Motor and transformer protection relays; different application logic.

 

Frequently Asked Questions (FAQ)

What does “CE446BB1NH” actually mean?
C = IEC standard; E4 = 1 A CT inputs; 46 = 4 binary inputs + 6 binary outputs; B = Modbus RTU / IEC 60870-5-103 RS-485. The remaining characters define regional/firmware or accessory variants. Confirm with the OEM nameplate.Can I use this on 5 A CTs?
Not directly. The E4 version is for 1 A secondary CTs. If your CTs are 5 A, you need the D4 variant or verified interposing CTs. Otherwise pickup values will be wrong.Does it support IEC 61850?
No. This order code supports Modbus RTU and IEC 60870-5-103 over RS-485. If your substation runs IEC 61850, you will need a gateway or a newer IED.Is auto-reclose safe on cable feeders?
Usually not. Auto-reclose is more appropriate for overhead lines where faults may be transient. On cable feeders, repeated reclosing can worsen insulation damage.Can I hot-swap this relay?
Electrically, the auxiliary supply is wide-range, but you should not replace it while the feeder is energized unless your switching procedure, CT shorting, and trip-circuit design explicitly allow it. Treat CT open-circuit risk as the primary hazard.What should I check before accepting stock?
Order code label, firmware version, physical damage, terminal condition, communication test, and a basic secondary injection report. If the seller cannot provide any test evidence, treat it as unverified.Is this still an ABB-supported product?
REF601 is a legacy Relion 605 series relay. ABB has moved newer projects toward later Relion families. For long-term standardization, plan a migration path, but REF601 remains serviceable as a like-for-like spare when verified.