Key Technical Specifications
- Product Model: IC610MDL179
- Manufacturer: GE Fanuc
- Product Category: AC Output Module
- Voltage Rating: 115/230 VAC
- Circuit Count: 8 Independent Circuits
- Output Type: AC Switching (Relay)
- Series Compatibility: Series One PLC
- Mounting Style: Backplane Plug-In
- Operating Temp: Industrial Standard Range
- Origin: Manufactured in Japan
Product Introduction
The GE IC610MDL179 is an 8-circuit AC output module designed for the Series One PLC platform. It switches 115/230 VAC field devices such as contactors, solenoids, and indicator lamps.This module provides isolated switching for each of its eight circuits. Field technicians appreciate the individual status LEDs per circuit, which make troubleshooting blown fuses or stuck relays significantly faster during midnight callouts.
Installation & Configuration Guide
Preparation (10 min):
Lock out and tag out all AC field power. Verify the backplane slot assignment in your Series One configuration. Gather a multimeter rated for AC voltage and appropriate insulated tools.Removal (5–10 min):
Disconnect all field wiring from the terminal block. Press the release lever and rotate the module outward. Never pull by the wires.Installation (10 min):
Align the IC610MDL179 with the backplane guides. Rotate inward until the lever locks. Reconnect field wiring according to the terminal diagram. Double-check every connection.Power-On & Test (10 min):
Restore AC field power. Use your programming software to force each output individually. Verify the LED illuminates and the field device actuates. Measure output voltage at the terminal block under load.
Troubleshooting Quick Reference
- No Output LED: Check field fuse and AC supply voltage.
- LED On But No Output: Measure voltage across output terminals. Relay may be welded open.
- Intermittent Operation: Inspect terminal screws for proper torque. Loose connections cause arcing.
- Module Not Responding: Verify backplane seating. Reseat the module firmly.
- All Outputs Dead: Check the Series One power supply capacity and backplane integrity.
Dimensions, Mounting & Wiring Notes
- Dimensions: Standard Series One single-width footprint
- Mounting: Backplane connector with locking lever
- Wiring: Use 18-22 AWG stranded wire. Torque terminals to 7 in-lbs.
- Terminal Type: Removable screw terminal block
- Caution: Always disconnect AC power before servicing. Arc flash hazard.
FAQ
Can I use this module for DC loads?
No. The IC610MDL179 is strictly an AC output module. Using it for DC loads will damage the relay contacts. Always verify load type first.I have an IC610MDL179A. Is this the same part?
The base model is compatible, but always check the suffix. The “A” revision may have minor internal differences. Photograph your existing module before ordering.What is the maximum load per circuit?
Check the OEM datasheet for exact ratings. Exceeding the per-circuit current limit is the most common cause of premature failure. Leave a 20% safety margin.Do you test these before shipping?
Yes. Every module undergoes a 24-hour live rack test on a Series One backplane. We verify all 8 circuits and generate a test report. Function verified under test conditions.Is there a warranty?
12 months. If it fails under normal use, we replace it. No restocking fees for defective units.How do I know it is genuine GE Fanuc?
We verify origin through serial number cross-referencing and physical inspection. Counterfeit modules are a real risk in legacy markets. We only sell verified authentic parts.Can I replace this with a newer Series 90-30 module?
No. Series One and Series 90-30 use different backplanes and form factors. Migration requires a full system redesign. Consult a GE Fanuc integrator for upgrade paths.