ABB CI858K01 | DriveBus Interface Module In Stock

  • Model: CI858K01 (3BSE018135R1)
  • Brand: ABB
  • Series: AC 800M I/O & Communication
  • Core Function: Provides a DriveBus interface to connect ABB drives and specialized I/O units to an AC 800M controller.
  • Type: Communication Interface Module
  • Key Specs: 8 Mbit transmission speed, CEX bus powered, hot-swap support.
Category:

Description

Key Technical Specifications

Parameter Details
Part Number CI858K01 / 3BSE018135R1
Manufacturer ABB
Product Type DriveBus Interface Module
Protocol ABB DriveBus (Master/Slave)
Transmission Speed 8 Mbit
Power Supply Powered via CEX bus (No external 24V required)
Current Consumption 200 mA
Hot Swap Supported (with AC 800M rack)
Operating Temp Up to 55°C
Protection Rating IP20 (EN 60529, IEC 529)
Width 59 mm
Height 185 mm
Depth 127.5 mm
Weight 0.7 kg (including base unit)

 

Product Introduction

If you’re running ABB drives on an AC 800M controller, you already know the headache of third-party gateways. The CI858K01 is the native solution. I’ve used these on paper machines and rolling mills where segment drive communication has to be flawless. It connects directly to the CEX bus, meaning you don’t have to run a separate 24V power supply just to keep the comms alive. The processor unit handles the power delivery.What I actually care about is the hot-swap capability and the physical footprint. You can swap this thing out without taking down the whole rack, which is a lifesaver during a production run. It handles up to 24 ABB drives per module. Just remember, if you’re chaining multiple drives, you’ll need an NDBU branching unit to build that logical bus over a physical star topology. It’s a straightforward piece of hardware, but it demands respect for the DriveBus protocol timing.

Quality SOP & Tech Pitfalls

The Lab Report (SOP)
Before this module goes in a box, it goes through my rack. I don’t ship blind.

  • Visual/Counterfeit Check: Inspecting the PCB silkscreen and the TP858 base unit connections. I’m looking for micro-fractures on the CEX bus pins.
  • Live Test: Seated on a test AC 800M PM861. I verify the CEX bus handshake and check the DriveBus LED status.
  • Multimeter Checks: Fluke 115 on the optical connectors to ensure no short circuits to the chassis.
  • Firmware Logging: Checking the internal revision against the OEM datasheet.
  • Anti-static Sealing: Bagged with desiccant. Humidity kills these boards faster than heat.

The Engineer’s Warning (Pitfalls)
Do not mess with the NDBU branching units. I once saw a tech daisy-chain three NDBUs without checking the physical star topology requirements. The DriveBus timing skewed, and the controller started dropping drives randomly. It looked like a failing CI858, but it was bad topology. Also, this module is hot-swappable, but only if the AC 800M rack supports it and you know what you’re doing. Pulling it during a heavy I/O scan can still cause a brief bus fault.

 

Installation & Configuration Guide

Phase 1: Pre-Installation

  • ⚠️ Verify Topology: Map out your NDBU branching units. Ensure you aren’t exceeding the 24-drive limit per CI858.
  • ⚠️ ESD Protection: Strap on your wristband. The CEX bus pins are highly sensitive to static discharge.

Phase 2: Removal

  • Label the optical DriveBus cables. They look identical, but plugging them into the wrong NDBU port will cause a comm fault.
  • Release the DIN clips on the TP858 base unit carefully. Don’t force it; the plastic tabs snap if you yank them.

Phase 3: Installation

  • Seat the Module: Push the CI858K01 firmly into the TP858 base until the DIN clips lock. You need a solid mechanical connection for the CEX bus to register.
  • Check Base Unit: Ensure the TP858 base is securely fastened to the mounting plate. Vibration will loosen it over time.

Phase 4: Power-On & Testing

  • Verify CEX Power: The module should light up immediately via the CEX bus. No external 24V needed.
  • LED Check: Watch the DriveBus status LEDs. A steady green means the master/slave handshake is successful. Flashing red indicates a topology or cable issue.
  • Controller Verification: Open Compact Control Builder. Confirm the CI858 is online and all connected ABB drives are communicating without timeouts.

Compatible Replacement Models

  • ✅ Drop-in Replacement: CI858K01 (3BSE018135R1). Exact same part. If you’re upgrading from an older revision, just swap it.
  • ⚠️ Software Compatible: CI860K01 (3BSE032444R1) or CI865K01 (3BSE040795R1). These are newer DriveBus/Fieldbus modules. They will physically fit the TP858 base, but you must update the hardware description in Control Builder and potentially recompile the logic. Expect a few hours of engineering time.
  • ❌ Hardware Mod Required: CI853K01 (3BSE018103R1) or CI854AK01 (3BSE030220R1). These are Ethernet/PROFINET modules. They use a completely different base unit and protocol. Do not buy these unless you are completely rewiring the drive network to industrial Ethernet.

 

Frequently Asked Questions (FAQ)

Can I hot-swap this safely while the plant is running?
Yes, but with a caveat. The AC 800M system supports hot-swapping for the CI858. However, if you pull it while the controller is executing a heavy DriveBus polling cycle, you might trigger a brief fault tag. It won’t crash the CPU, but your HMI will flash red for a second. Best practice is to swap it during a low-traffic window if possible.Does this module need a separate 24V power supply?
No. This is one of the best things about it. The CI858 draws its 200 mA directly from the CEX bus via the processor unit. If you’re trying to wire 24V to it, you’re doing it wrong and might fry the board.How many drives can I connect to a single CI858?
The hard limit is 24 ABB drives. But if you’re using more than one, you absolutely need an NDBU branching unit to handle the physical star topology. The DriveBus protocol is strict about signal reflection.What happens if the CEX bus connection is loose?
The module won’t power up. You’ll get no LEDs, and the controller will throw a “Module Missing” or “CEX Bus Error” in Control Builder. Reseat the module. If it still fails, check the TP858 base unit pins for corrosion or bending.Is the TP858 base unit included when I buy this?
Usually, yes. The standard order 3BSE018135R1 includes the CI858 communication interface and the TP858 base unit. But always verify the packing list. Sometimes suppliers split them up.Can I use this with non-ABB drives?
Not natively. The DriveBus protocol is proprietary to ABB. If you want to connect a Siemens or Rockwell drive, you need to look at the CI854A (PROFINET) or CI853 (EtherNet/IP) modules instead.