Key Technical Specifications
| Parameter | Value |
|---|---|
| Part / Module | 8101-HI-TX-02 |
| Platform | GE PAC8000 Modular I/O |
| Input Channels | 8 single-ended |
| Nominal Signal Range | 4–20 mA |
| Full Signal Range | 1–23 mA |
| Resolution | 16-bit |
| Response Time | 27 ms max in 4–20 mA mode |
| HART Response | 0.75 sec per point |
| HART Support | HART pass-through; HART variable and status reporting |
| Fault Detection | Open-circuit and short-circuit detection |
| Bus Field Power | 24 V DC ±10% |
| Accuracy | ±0.1% of span over temperature range |
Product Introduction
GE 8101-HI-TX-02 is a GE PAC8000 modular I/O analog input module. It accepts eight single-ended 4–20 mA field signals and converts them for use by a PAC8000 controller or distributed I/O system.The module is intended for process measurement applications where 4–20 mA transmitters must be read with defined accuracy, fault detection, and HART data access. Its 16-bit resolution, 27 ms response time, and HART pass-through make it suitable for temperature, pressure, flow, level, or other analog process signals — but only when the host system, terminal assembly, and field power match the module requirements.
Installation & Configuration Guide
Preparation — 10 min
- Confirm the module label reads 8101-HI-TX-02.
- Record the module key code — expected to be A1 for this configuration.
- Identify the PAC8000 rack, rail bus position, and terminal assembly.
- Confirm field devices are 4–20 mA transmitters, either 2-wire or 4-wire.
- Confirm 24 V DC ±10% bus field power is available if required by the transmitter wiring.
- Prepare ESD protection: wrist strap, grounded mat, anti-static bag.
- Photograph the existing module, terminal block, wiring, and module key before removal.
Removal — 5–10 min
- Place the controller or I/O rack in a safe maintenance state.
- De-energize field power where safe and permitted.
- Apply lockout/tagout if the panel or field wiring is exposed.
- Label every field wire before disconnecting.
- Remove the terminal assembly if required by the PAC8000 mounting method.
- Release the module from the rail/bus.
- Do not pry connectors or force the module sideways.
Installation — 10 min
- Inspect the replacement module for bent pins, corrosion, cracked housing, or burn marks.
- Confirm the module key matches the original module key.
- Align the module with the rail/bus before seating it.
- Press the module firmly into place until it seats fully.
- Reinstall the terminal assembly in the correct orientation.
- Reconnect field wiring exactly as labeled.
- For 2-wire transmitters, verify polarity and loop power path.
- For 4-wire transmitters, verify separate power and signal connections.
Power-On & Test — 10 min
- Restore 24 V DC field power within ±10%.
- Restore rack/bus power only after wiring is verified.
- Check that the controller recognizes the module.
- Confirm each channel shows a valid 4–20 mA reading.
- Force a simulated open circuit on one spare channel to verify open-circuit detection, if safe.
- Force a simulated short circuit on one spare channel to verify short-circuit detection, if safe.
- If HART is used, confirm HART pass-through and variable/status reporting are enabled in the configuration.
Troubleshooting Quick Reference
| Symptom | Most Likely Cause | First Check |
|---|---|---|
| Controller does not see the module | Wrong slot, bad bus contact, or wrong module key | Reseat module; verify A1 key code |
| All channels read 0 mA | Field power missing or wiring open | Measure 24 V DC field supply |
| One channel reads open | Broken wire, loose terminal, or failed transmitter | Check terminal torque and loop continuity |
| One channel reads shorted | Cable damage, terminal short, or wiring error | Disconnect field wire and retest |
| HART device not detected | HART reporting disabled or wiring issue | Enable HART variable/status reporting |
| Erratic readings | EMI, poor grounding, or shared conduit with power cables | Separate signal wiring; check shielding |
| Module feels hot | Excess bus current or wrong module type | Measure 12 V rail and 24 V field current |
Dimensions, Mounting & Wiring Notes
- Module width: 42 mm
- Module weight: approximately 200 g
- Mounting: PAC8000 modular I/O rail/bus installation
- Terminal assemblies: use the terminal type specified for the installed field wiring
- Field wiring: confirm 2-wire or 4-wire transmitter connection before power-up
- Power: 24 V DC ±10% bus field power required for transmitter loop power
- Isolation note: channels are not isolated from each other
FAQ
Is GE 8101-HI-TX-02 an analog input or a network switch?
It is an analog input module. Some unrelated listings describe it as a network switch or camera module, but those descriptions do not match the PAC8000 8-channel 4–20 mA input function.Can I use 0–10 V sensors with this module?
Not without verification. The documented input range is 4–20 mA, with a full detection range of 1–23 mA. Do not connect voltage-output sensors unless the PAC8000 manual explicitly supports it for this module.Does this module support HART?
Yes. It supports HART pass-through and HART variable/status reporting. HART response is approximately 0.75 sec per point, while standard 4–20 mA response is 27 ms max.I have a 2-wire transmitter. Will this module power it?
It can support 2-wire transmitters using 24 V DC bus field power, with up to 300 mA max for 2-wire transmitter loads. For 4-wire transmitters, the limit is 60 mA max per transmitter.What happens if a field wire breaks?
The module provides open-circuit detection. Below approximately 0.5 mA, the channel should flag an open/low fault condition, depending on system configuration.Can I replace another GE analog input module with 8101-HI-TX-02?
Only if the replacement matches channel type, signal range, module key, terminal assembly, and PAC8000 configuration. A physically similar module is not automatically compatible.Is this module intrinsically safe?
The documentation references FM non-incendive field wiring parameters, not full intrinsic safety. For hazardous-area installations, verify the exact terminal assembly, wiring method, and approval markings before commissioning.