Key Technical Specifications
- Product Model: UR9EH
- Manufacturer: GE Multilin
- Function: Universal Relay CPU / Logic Processor
- Logic Engine: FlexLogic™ programmable logic
- Operating Temp: -40°C to +80°C
- Humidity: Up to 95% non-condensing at 55°C
- Communication: Ethernet, Modbus, DNP3, IEC 61850
- I/O Interface: Virtual I/O, Hardwired Contact I/O
- Analog Support: RTD, 4-20mA, Voltage inputs
- Mounting: Vertical or Horizontal (3/4 size)
- Certification: UL Listed, CE Marked
- Origin: Canada
Product Introduction
The GE UR9EH serves as the central processing unit for the Multilin UR series, handling protection logic, metering, and control for generators and transformers. It executes FlexLogic™ equations and manages virtual I/O signals without requiring external hardwiring for internal logic.Field engineers specify the UR9EH for its wide -40°C to +80°C operating range and deterministic processing speed. This module replaces older 9A/9C/9D CPUs but requires matching new-generation CT/VT modules to prevent DSP errors.
Installation & Configuration Guide
Preparation (10 min)
- Verify system power is OFF and locked out.
- Confirm CT/VT modules match the “New” CPU generation.
- Have Enervista UR Setup software ready.
Removal (5–10 min)
- Disconnect Ethernet and serial cables.
- Release the front panel locking mechanism.
- Slide the CPU module straight out.
- Inspect backplane pins for damage.
Installation (10 min)
- Align the UR9EH with the backplane guides.
- Slide in firmly until fully seated.
- Engage the front panel locking latch.
- Reconnect communication cables.
Power-On & Test (10 min)
- Apply control power.
- Watch for the “System OK” LED.
- Check Enervista for “DSP Error” or “Hardware Mismatch.”
- Verify FlexLogic™ equations are running.
- Test a virtual output via the HMI.
Troubleshooting Quick Reference
- DSP Error: CT/VT module generation mismatch. Verify 9E vs 9A hardware.
- No Display: Check 18.5-36 VDC supply at backplane.
- Comm Loss: Verify Ethernet port LED status and IP config.
- Logic Fail: FlexLogic™ scan time exceeded. Reduce equation complexity.
- High Temp: Ensure airflow is not blocked. Max ambient is 80°C.
Dimensions, Mounting & Wiring Notes
- Form Factor: 3/4 Size Universal Relay
- Mounting: Vertical or Horizontal orientation supported
- Backplane: Standard UR series backplane connector
- Wiring: No field wiring on CPU. Connect via backplane only.
- Cooling: Ensure 50mm clearance above/below for convection.
FAQ
Can I put a UR9EH in an old G60 rack?
Yes, but you must replace the CT/VT modules with the new generation. Mixing old VTs with a 9E CPU causes DSP errors.I see a “Hardware Mismatch” alarm. What now?
This confirms a generation mismatch. The UR9EH (9E) cannot run with 9A/9C/9D analog modules. Swap the analog modules first.Does this support IEC 61850?
Yes, the UR9EH supports IEC 61850 Ed 1 and Ed 2 via the Ethernet port. Check your license key in Enervista.What is the max operating temperature?
The GE UR9EH is rated for -40°C to +80°C ambient. Derate if installed in a sealed enclosure without ventilation.Is FlexLogic™ included?
Yes, the UR9EH has built-in FlexLogic™ capacity. No extra license is needed for basic logic, only for advanced IEC 61850 features.Do you have the manual?
We include the GE Multilin UR Series Instruction Manual (GEK-113300) with every shipment.I need a replacement fast. Is this in stock?
Inventory moves daily. Contact us for real-time stock status on the GE UR9EH.