Description
Key Technical Specifications (For Spare Part Verification)
- Product Model: F6217
- Manufacturer: HIMA Paul Hildebrandt GmbH
- System Compatibility: HIMatrix F60 series safety controllers
- Output Channels: 8 isolated digital outputs
- Output Type: Dry contact relay (form C), rated for 2 A @ 30 VDC / 250 VAC
- Redundancy Architecture: Integrated into HIMatrix’s triple-modular redundant (TMR) voting logic
- Diagnostic Coverage: >99% for dangerous failures per original FMEDA
- Response Time: <10 ms typical (from logic command to contact closure)
- Isolation: Channel-to-channel and channel-to-backplane per IEC 61508
- Mounting: Hot-pluggable in HIMatrix F60 I/O chassis
- LED Indicators: Per-channel status (energized/de-energized), module OK, and fault indication
System Role and Downtime Impact
The F6217 serves as the final output stage in HIMatrix F60-based Safety Instrumented Systems (SIS), commonly used to command solenoid valves, motor contactors, or alarm relays during emergency events. It receives trip commands from the safety logic solver and actuates field devices in a fail-safe manner—typically de-energizing on demand to close an ESD valve or stop a pump. Because it directly interfaces with high-energy circuits, its reliability is critical. A failed F6217 can result in either a spurious trip (causing unplanned downtime) or, more severely, a failure to trip when required—posing significant process safety and environmental risks. In regulated industries, such a failure could violate compliance with IEC 61511 and trigger regulatory scrutiny.
Reliability Analysis and Common Failure Modes
Despite its robust design, the F6217 is subject to predictable wear mechanisms due to its electromechanical components. The most common failure mode is relay contact degradation, including oxidation, pitting, or welding caused by arcing—especially when switching inductive loads without proper suppression. Internal optocoupler aging can lead to signal transmission delays or open-circuit faults between redundant channels. Additionally, terminal block screw loosening over time (due to vibration or thermal cycling) may cause intermittent connections, leading to erratic output behavior that may not be immediately flagged by diagnostics.
A key vulnerability lies in the mechanical life rating of the relays (typically 100,000–500,000 operations). In applications with frequent partial-stroke testing or nuisance trips, this limit may be reached sooner than expected. Units operated near current or voltage limits show accelerated contact erosion.
Recommended preventive actions include:
- Conducting regular proof tests that verify both de-energize-on-trip and return-to-normal behavior
- Measuring contact resistance during maintenance windows to detect early degradation
- Ensuring proper snubber circuits or flyback diodes are installed on inductive field loads
- Monitoring HIMatrix diagnostic logs for “output mismatch” or “voting disagreement” alarms

HIMA F6217
Lifecycle Status and Migration Strategy
HIMA has officially obsoleted the F6217 as part of the HIMatrix F60 platform end-of-life plan. No new modules are manufactured, and factory repair services are no longer available. Continued reliance on this module increases exposure to supply chain disruption and functional safety audit findings.
Short-term mitigation includes:
- Securing multiple tested spares with matching hardware revisions and diagnostic baselines
- Validating hot-swap functionality and redundancy behavior in a test rack before storage
- Maintaining detailed records of channel usage and operational cycles to prioritize replacement
For long-term sustainability, HIMA recommends migration to the HIMax X platform. The functional successor is the DO-X208, an 8-channel TMR digital output module with enhanced diagnostics, solid-state options, and PROFINET/OPC UA connectivity. Migration involves:
- Replacing the HIMatrix F60 controller with a HIMax X CPU and I/O chassis
- Using terminal block adapters to retain existing field wiring where possible
- Revalidating all SIF logic, response times, and proof test procedures under IEC 61511
- Upgrading engineering tools to HIMA Safety Suite
While requiring capital investment, this transition restores access to manufacturer support, cybersecurity updates, and extended lifecycle assurance—essential for facilities planning operation beyond 2030. A risk-based, phased migration approach is advised to balance safety, cost, and operational continuity.