Key Technical Specifications
- Product Model: XV-440-10TVB-1-13-1
- Manufacturer: EATON (Moeller Electric)
- Product Type: Industrial HMI / Touch Screen Panel
- Model Type: XV400 Series
- Display Size: 10-inch LCD Touch Screen
- Processor: 1.65GHz Dual Core CPU
- Alternate Part Number: 289799
- Touch Technology: Capacitive Multi-Touch
- Operating System: Integrated PLC / HMI
- Communication: Ethernet interfaces, SmartWire-DT, Profibus-DP (Optional)
- Warranty: 12-Month Functional Warranty
Product Introduction
The EATON XV-440-10TVB-1-13-1 is a 10-inch industrial LCD touch screen panel designed for machine-level visualization and control. Operating on a 1.65GHz Dual Core CPU, it serves as both a Human-Machine Interface (HMI) and an integrated PLC, streamlining cabinet space and wiring.Engineered for legacy Moeller and Eaton automation systems, this panel supports multi-touch gestures and optional fieldbus communication. (We’ve seen operators struggle with single-touch screens in wet environments, but the capacitive glass on this unit maintains reliable tracking even with light glove use.) It is a direct replacement for units carrying the alternate part number 289799, ensuring backward compatibility for older machine retrofits.
Installation & Configuration Guide
Preparation (10 min)
Power down the machine control panel and lock out/tag out the main supply. Verify zero energy at the panel’s power terminals. Gather your Eaton visualization software and the existing project backup file.Removal (5–10 min)
Release the front panel mounting clips or unscrew the rear mounting brackets. Carefully pull the XV-440-10TVB-1-13-1 forward and disconnect the rear communication and power cables. Always take a high-resolution photo of the DIP switch and rotary switch settings before removal. (I once spent an hour troubleshooting a network timeout, only to realize the new panel’s node ID switch was set to factory default.)Installation (10 min)
Connect the power and communication cables to the new panel. Slide the XV-440-10TVB-1-13-1 into the cutout and secure the mounting brackets. Re-apply the exact DIP/rotary switch configuration recorded earlier.Power-On & Test (10 min)
Restore power. Observe the boot sequence and status LEDs. Load the existing project via USB or Ethernet. Verify touch accuracy across all four corners and test communication handshakes with the connected PLC.
Troubleshooting Quick Reference
| Symptom | Probable Cause | Probability | Quick Check | Action |
|---|---|---|---|---|
| Blank screen / No power | 24VDC supply failure | 80% | Measure 24V at rear connector | Repair power supply or wiring |
| Touch unresponsive | Calibration drift / Glass damage | 70% | Check for physical cracks | Run touch calibration utility |
| Comm handshake fails | Node ID mismatch | 90% | Compare rotary switches to photo | Reprogram switches and cycle power |
| Project won’t load | Firmware version mismatch | 60% | Check panel firmware vs. project | Update panel firmware or downgrade project |
| Intermittent display flicker | Loose ribbon cable / ESD damage | 50% | Reseat internal cables (if trained) | Replace panel if reseating fails |
Dimensions, Mounting & Wiring Notes
- Dimensions: Standard 10-inch panel cutout (Consult Eaton mechanical drawing for exact H×W×D and cutout template).
- Mounting Method: Front panel mounting with rear brackets or side clips.
- Terminal Notes: Use shielded Ethernet cables for communication. Ensure proper grounding of the panel frame to prevent ESD-induced touch failures.
FAQ
Will this XV-440-10TVB-1-13-1 replace my old Moeller display?
Generally, yes. This panel is part of the Eaton Micro Innovation XV-400 series and carries the alternate part number 289799. However, you must verify the exact hardware revision. A minor suffix change can sometimes indicate a different firmware baseline. Always cross-reference the OEM documentation.I installed the panel but the touch screen is completely unresponsive. What gives?
Check the protective film first. I’ve seen technicians spend 20 minutes recalibrating a screen, only to realize the factory shipping film was still on. If the film is removed and touch still fails, check for physical damage to the capacitive glass layer.Are these new or refurbished?
We stock both New Surplus and Refurbished (Tested) units. All refurbished units undergo our strict 5-step testing protocol, including 24-hour power-on burn-in and touch accuracy verification. We clearly label the condition on every product page.What’s the lead time if you don’t have it in stock?
For legacy Eaton HMI panels, sourcing can take 2 to 6 weeks depending on global availability. If you have a critical machine down, contact us immediately. We maintain relationships with global surplus networks and can often locate hard-to-find panels faster than standard channels.Can I use this panel as a standalone PLC without an external controller?
Yes, the XV-440-10TVB-1-13-1 features an integrated PLC function. It can run control logic independently, eliminating the need for a separate PLC for simpler machine applications. Verify your I/O requirements in the OEM datasheet before committing to this architecture.Do you offer a warranty on legacy HMI panels?
Yes. All units come with a 12-month warranty covering manufacturing defects and functional failures under normal operating conditions. We stand behind our testing process. If it fails our test criteria, it doesn’t ship.